5.14
Troubleshooting Fieldbus Diagnostics
If you see a measurement labeled
BAD
or
CHECK
, tap
Details
to view the values for each
measurement. Press and hold a measurement value on the screen to view Help that
describes overview or troubleshooting information. You can also access the Help menu by
holding the checkmark button on the keypad when a measurement value is selected.
Note
To prevent inaccurate
BAD
or
CHECK
readings, review the measurement criteria in the
Settings
, and
set the minimum and maximum values to ensure they are appropriate for your installation.
Help text example
Figure 5-11:
DC voltage measurement
Possible cause
Action
Lower than expected
The power supply's voltage
setting may be set too low.
Verify the power supply's
voltage setting is correct. If
necessary, increase the power
supply voltage.
An unexpected voltage drop
may be due to a damaged
cable, corrosion in the
terminals, low impedance to
ground, water in the device
terminals, or loose connections.
Measure the voltage at several
points on the fieldbus segment
to determine the location of the
unexpected voltage drop. Start
at the power supply and
continue toward the original
measurement point where the
voltage was measured low.
Fieldbus Diagnostics application
174
User Guide
Summary of Contents for AMS Trex
Page 1: ...User Guide Rev 3 August 2017 AMS Trex Device Communicator User Guide ...
Page 8: ...Contents vi User Guide ...
Page 130: ...Field Communicator application 122 User Guide ...
Page 186: ...Fieldbus Diagnostics application 178 User Guide ...
Page 198: ...Technical specifications 190 User Guide ...
Page 206: ...Glossary 198 User Guide ...