One connection option for connecting to the fieldbus segment
Figure 5-6:
A. Terminators
B. Power conditioner
C. Fieldbus power supply
D. Host system
2.
Open
Fieldbus Diagnostics
.
The Trex unit connects to the device/fieldbus segment and begins the
measurements.
3.
Optional - Tap
Go Online
to query devices for their tags.
5.7
Measure the DC voltage, noise, and the fieldbus
signal
The Fieldbus Diagnostics Overview screen displays a GOOD, BAD, or CHECK status for the
measurements to give you a quick summary. Check the measurement criteria in the
Settings
to ensure they are appropriate for your installation.
You can view the actual measurement values by tapping Details on the Fieldbus
Diagnostics Overview screen.
Note
Before taking a noise measurement, remove the AC adapter from the Trex unit, if it is connected.
This isolates the Trex unit from the local power grid.
Procedure
1.
If the FOUNDATION fieldbus device is externally-powered, do the following:
a. Connect the lead set to the FF terminals on the Trex unit and to the fieldbus
segment or device.
b. Open
Fieldbus Diagnostics
.
Fieldbus Diagnostics application
User Guide
159
Summary of Contents for AMS Trex
Page 1: ...User Guide Rev 3 August 2017 AMS Trex Device Communicator User Guide ...
Page 8: ...Contents vi User Guide ...
Page 130: ...Field Communicator application 122 User Guide ...
Page 186: ...Fieldbus Diagnostics application 178 User Guide ...
Page 198: ...Technical specifications 190 User Guide ...
Page 206: ...Glossary 198 User Guide ...