Avoid placing sensitive signal circuits in a zone 300mm (12in) all around
the power module.
Figure 4-26 Sensitive signal circuit clearance
Ensure good EMC grounding.
Figure 4-27 Grounding the drive, motor cable shield and filter
Connect the shield of the motor cable to the ground terminal of the motor
frame using a link that is as short as possible and not exceeding 50mm
(2in) long. A full 360
°
termination of the shield to the terminal housing of
the motor is beneficial.
It is unimportant for EMC purposes whether the motor cable contains an
internal (safety) ground core, or there is a separate external ground
conductor, or grounding is through the shield alone. An internal ground
core will carry a high noise current and therefore it must be terminated
as close as possible to the shield termination.
Figure 4-28 Grounding the motor cable shield
Unshielded wiring to the optional braking resistor(s) may be used,
provided the wiring does not run external to the enclosure. Ensure a
minimum spacing of 300mm (12in) from signal wiring and the AC supply
wiring to the external EMC filter. Otherwise this wiring must be shielded.
Figure 4-29 Shielding requirements of optional external braking
resistor
Sensitive
signal
cable
≥
300mm
(12in)
Ensure direct
metal contact
at drive and
filter mounting
points (any
paint must be
removed).
Motor cable shield
(unbroken) electrically
connected to and held
in place by grounding
clamp.
+DC
BR
Optional external
braking resistor
Enclosure
+DC
BR
Optional external
braking resistor
Enclosure