Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
62
Affinity User Guide
www.controltechniques.com Issue Number: 5
3.10 Electrical terminals
3.10.1 Terminal sizes and torque settings
Table 3-10 Drive control and relay terminal data
Table 3-11 Wall mounted drive power terminal data
Table 3-12 Plug-in terminal block maximum cable sizes
Table 3-13 Schaffner external EMC filter terminal data (size 1 to 6)
Table 3-14 Epcos external EMC Filter terminal data
To avoid a fire hazard and maintain validity of the UL listing,
adhere to the specified tightening torques for the power and
ground terminals. Refer to the following tables.
Model
Connection type
Torque setting
All
Plug-in terminal block
0.5 N m (0.4 lb ft)
Model
size
AC terminals
High current DC
and braking
Ground terminal
Term.
Max
torque
Term.
Max
torque
Term.
Max
torque
1
Plug-in
terminal
block
1.5 N m
(1.1 lb ft)
Terminal
block (M4
screws)
1.5 N m
(1.1 lb ft)
M5 stud
4.0 N m
(1.9 lb ft)
2
Plug-in
terminal
block
1.5 N m
(1.1 lb ft)
Terminal
block (M5
screws)
1.5 N m
(1.1 lb ft)
M5 stud
4.0 N m
(1.9 lb ft)
3
Terminal
block (M6
screws)
2.5 N m
(1.8 lb ft)
Terminal
block (M6
screws)
2.5 N m
(1.8 lb ft)
M6 bolt
4.0 N m
(1.9 lb ft)
4
M10 stud
15 N m
(11.1 lb ft)
M10 stud
15 N m
(11.1 lb ft)
M10 stud
12.0 N m
(8.8 lb ft)
5
M10 stud
15 N m
(11.1 lb ft)
M10 stud
15 N m
(11.1 lb ft)
M10 stud
12.0 N m
(8.8 lb ft)
6
M10 stud
15 N m
(11.1 lb ft)
M10 stud
15 N m
(11.1 lb ft)
M10 stud
12.0 N m
(8.8 lb ft)
Model size
Terminal block description
Max cable size
All
11 way control connectors
1.5 mm
2
(16 AWG)
All
2 way relay connector
2.5 mm
2
(12 AWG)
1 and 2
6 way AC power connector
8 mm
2
(8 AWG)
4, 5 and 6 Low Voltage DC Enable connector 1.5 mm
2
(16 AWG)
6
Heatsink fan supply connector
1.5 mm
2
(16 AWG)
All
BAN connector
1.5 mm
2
(16 AWG)
WARNING
CT part
number
Power
connections
Ground
connections
Max cable
size
Max torque
Ground
stud size
Max torque
4200-6118
4mm
2
12AWG
0.8 N m
(0.6 lb ft)
M5
3.5 N m
(2.6 lb ft)
4200-6119
4200-6210
10mm
2
8AWG
2 N m
(1.5 lb ft)
M5
3.5 N m
(2.6 lb ft)
4200-6305
16mm
2
6AWG
2.2 N m
(1.6 lb ft)
M6
3.9 N m
(2.9 lb ft)
4200-6307
4200-6309
4200-6406
50mm
2
0AWG
8 N m
(5.9 lb ft)
M10
25 N m
(18.4 lb ft)
4200-6408
25mm
2
4AWG
2.3 N m
(1.7 lb ft)
M6
3.9 N m
(2.9 lb ft)
4200-6503
95mm
2
4/0AWG
20 N m
(14.7 lb ft)
M10
25 N m
(18.4 lb ft)
4200-6504
50mm
2
0AWG
8 N m
(5.9 lb ft)
M10
25 N m
(18.4 lb ft)
4200-6603
M10
25 N m
(18.4 lb ft)
4200-6604
CT part
number
Power
connections
Ground
connections
Max cable
size
Max torque
Ground
stud size
Max torque
4200-6120
4mm
2
12AWG
0.6 N m
(0.4 lb ft)
M5
3.0 N m
(2.2 lb ft)
4200-6121
4200-6211
10mm
2
8AWG
1.35 N m
(1.0 lb ft)
M5
3.0 N m
(2.2 lb ft)
4200-6306
16mm
2
6AWG
2.2 N m
(1.6 lb ft)
M6
5.1 N m
(3.8 lb ft)
4200-6308
10mm
2
8AWG
1.35 N m
(1.0 lb ft)
4200-6405
50mm
2
0AWG
6.8 N m
(5.0 lb ft)
M10
10 N m
(7.4 lb ft)
4200-6407
4200-6501
95mm
2
4/0AWG
20 N m
(14.7 lb ft)
4200-6502
4200-6601
4200-6602
Summary of Contents for Affinity