Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Affinity User Guide
13
Issue Number: 5 www.controltechniques.com
For size 1 to 6 standard drives, size 1 to 3 E12/54 drives, and size 1 to 3 E12/E66 drives, the continuous current ratings given are for maximum 40
°
C
(104
°
F),1000m altitude and 3.0kHz switching. For size 4 to 6 E12/54 drives, the continuous current ratings given are for maximum 35
°
C
(95
°
F),1000m altitude and 3.0kHz switching. For further information refer to section 12.1.1
Power and current ratings (Derating for switching
Table 2-3 575V Drive ratings (500V to 575V ±10%)
The power ratings above for model size 4 and larger are for the 690V drives when used on a 500V to 575V supply.
Table 2-4 690V Drive ratings (500V to 690V ±10%)
Model
Maximum continuous
output current
Nominal power
at 575V
Motor power
at 575V
Peak current
A
kW
hp
A
3501
5.4
3.0
3.0
5.9
3502
6.1
4.0
5.0
6.7
3503
8.4
5.5
7.5
9.2
3504
11
7.5
10
12.1
3505
16
11
15
17.6
3506
22
15
20
24.2
3507
27
18.5
25
29.7
4603
36
22
30
39.6
4604
43
30
40
47.3
4605
52
37
50
57.2
4606
62
45
60
68
5601
84
55
75
92
5602
99
75
100
108
6601
125
90
125
137
6602
144
110
150
158
Model
Maximum continuous
output current
Nominal power
at 690V
Motor power
at 690V
Peak current
A
kW
hp
A
4601
22
18.5
25
24.2
4602
27
22
30
29.7
4603
36
30
40
39.6
4604
43
37
50
47.3
4605
52
45
60
57.2
4606
62
55
75
68.2
5601
84
75
100
92
5602
99
90
125
108
6601
125
110
150
137
6602
144
132
175
158
3
4
55
56
4
55
56
Summary of Contents for Affinity
Page 274: ...0474 0000 05 ...