FB3000 RTU Personality Module Field Installation Guide 

D301872X012 

June 2021 

Remote Automation Solutions 

  

FB3000 Remote Terminal Unit (RTU)   

Personality Module (3CPU16) 
Field Installation Guide 

 

Summary of Contents for 3CPU16

Page 1: ...FB3000 RTU Personality Module Field Installation Guide D301872X012 June 2021 Remote Automation Solutions FB3000 Remote Terminal Unit RTU Personality Module 3CPU16 Field Installation Guide ...

Page 2: ...al Systems 29 CFR Part 1910 Subpart S dated April 16 1981 OSHA rulings are in agreement with the National Electrical Code You must also ground mechanical or pneumatic instruments that include electrically operated devices such as lights switches relays alarms or chart drives Important Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring personnel saf...

Page 3: ...backup system you have If replacing an I O personality module switch the associated I O to whatever manual control system you have 1 If you are replacing an existing personality module that is already wired with an identical personality module and if there is no fault with the terminal block leave wiring connected to the terminal block and disconnect the terminal block from the personality module ...

Page 4: ...r loosen the captive fastening screw at the top of the personality module and slide the module straight out of the slot Removing a Personality Module 3 Press the new replacement personality module into the slot until it is properly seated then tighten the captive fastening screw Replacing a Personality Module ...

Page 5: ...une 2021 3 If you replaced an existing personality module with an identical replacement and were able to re use the terminal blocks reattach the terminal block by pressing it into place otherwise wire the new terminal block as required Reattaching the Terminal Block ...

Page 6: ...nal block wiring follow the wiring instructions for your particular module If you need more detail than is presented here refer to the FB3000 RTU Instruction Manual D301851X012 Wiring Communication Ports on the CPU 3CPU16 Serial Ports COM1 Configured as RS 232 1 RS 232 port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 ...

Page 7: ...2021 5 COM1 Configured as RS 485 4 wire 1 RS 485 4 wire port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 COM1 Configured as RS 485 2 wire 1 RS 485 2 wire port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 ...

Page 8: ...2 June 2021 6 COM2 Configured as RS 232 1 RS 485 port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 COM2 Configured as RS 485 4 wire 1 RS 485 4 wire port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 ...

Page 9: ...d as RS 485 2 wire 1 RS 485 2 wire port on device 2 Cable shield connection to chassis ground use either pin 19 or 20 COM3 Configured as RS 485 2 wire 1 Enable AC termination using switch 2 RS 485 bus twisted pair required 3 Cable shield connection to chassis ground use either pin 19 or 20 ...

Page 10: ...le Field Installation Guide D301872X012 June 2021 8 COM4 Configured as RS 485 2 wire 1 Enable AC termination using switch 2 RS 485 bus twisted pair required 3 Cable shield connection to chassis ground use either pin 19 or 20 ...

Page 11: ...FB3000 Personality Module Field Installation Guide D301872X012 June 2021 9 Ethernet and Micro USB Ports Location of Ethernet and USB Ports 1 Ethernet Port 1 2 Ethernet Port 2 3 Micro A B USB Port ...

Page 12: ...ule Field Installation Guide D301872X012 June 2021 10 Wiring I O on the Mixed I O Module 3MIX12 Analog Input AI AI Wiring Using 1 5 Vdc or 4 20 mA 1 External Voltage Source 2 External Current Source 3 Power Supply 30VDC Max ...

Page 13: ...FB3000 Personality Module Field Installation Guide D301872X012 June 2021 11 AI Wiring Using Loop Power 1 External Current Source Analog Output AO AO Wiring ...

Page 14: ...llation Guide D301872X012 June 2021 12 Digital Input DI DI Wiring internal pull up enabled Digital Output DO Digital Output DO Wiring High Side Internal Switch with 24V Loop Supply 1 50 mA load max field device 2 High Side Switch INTERNAL ...

Page 15: ...21 13 DO Wiring Low Side Internal Switch 1 Power Supply 30VDC Max 2 50 mA load max field device 3 Low side switch internal 4 Suppression diodes 5 Relay coil or inductive load Digital Output DO Wiring Dry Contact Closure using 24V Loop Supply 1 500 mA load max field device ...

Page 16: ...ne 2021 14 Digital Output DO Wiring Dry Contact Closure img DO_Wiring_Example2 jpg cdr 1 500 mA load max field device 2 30VDC Max Power Supply 3 DOHI_1 DOLO_1 configured as an external low side switch LSS 4 DOHI_2 DOLO_2 configured as an external high side switch HSS ...

Page 17: ...Field Installation Guide D301872X012 June 2021 15 Pulse Input PI Pulse Input PI Wiring 1 External Device Because no power supply requires internal pull up to be enabled 2 External Device 3 30VDC Max Power Supply 4 Control signal ...

Page 18: ...services described or their use or applicability Remote Automation Solutions RAS reserves the right to modify or improve the designs or specifications of its products at any time without notice All sales are governed by RAS terms and conditions which are available upon request RAS accepts no responsibility for proper selection use or maintenance of any product which remains solely with the purchas...