Emerson Network Power Liebert Intellislot 485 Quick Start Manual Download Page 1

Liebert Intellislot

®

 485 Card

With Adapter

Quick Start Guide

I

NSTALL

• Locate the adapter mounting location in your Liebert equipment.
• Secure the Intellislot 485 Card with Adapter with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal 

block or P1 on the card (See equipment user manual for details).

• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal 

block; Pin 1 is at the far left, and Pin 2 is the middle pin.

C

ONNECT

 

THE

 C

ABLE

• Locate the blue serial configuration cable (null modem) that shipped 

with the card.

• Connect the configuration cable to the DB-9 port on the card and to a 

COM port on your PC.

C

ONFIGURE

 

THE

 C

ARD

• Use terminal emulation software, such as 

HyperTerminal

, to open a direct connec-

tion to the card. Use the data at right to 

configure the emulation software.

• Press 

Enter

 for the 

Main Menu

.

• Select the option for 

485 Network Set-

tings

 and press 

Enter

 to access the com-

munications settings.

• Enter 

1

 and press 

Enter

.

• Select 

Modbus Server

 to enable the Modbus application.

• At the next screen, enter 

3

 to access the screen to set the 

Server ID

 

(the ID default is 1, but may be any number up to 255).

• Press 

Esc

 to return to the Main Menu.

• Enter 

X

 and press 

Enter

 to exit HyperTerminal, save your changes 

and reboot the card.

TB3

(P1: +)

(P2: -)

(P3: NC)

P1 is on 

left end of 

terminal 

block.

TB2

(P1: +)

(P2: -);

P1 is at the

right side of 

terminal block.

P1

DB-9 

Port

TB1 (P1: +; P2: -); P1 is at the 

right side of terminal block.

Emulation Software
Configuration

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control: None