SETUP

The instrument shows:

1a) ->OFF

  1100uS

Pressing twice “RIGHT” key the display will show:

1b) ->ON

  1000uS

“1a)” and “1b)” are working range values. Every range is set by a value that operates relay output.

Using default values, the setpoint 1 will drive a pump that will increase the conductivity value. The

pump will switch on for uS values minor than 1000uS and switch off when reaches 1100uS: 

this is the

ON/OFF working mode.

 The difference between the two uS (1100 e 1000) is called HYSTERESIS.

 To avoid damaging the relay do not set Hysteresis under 100uS.

PROPORTIONAL mode

. The output relay is modulated (ON/OFF) depending on uS values set in 1a)

and 1b). Ex.: Proportional mode between 1100uS (0%) and 1000uS (100%). In this way the relay will

be on for values between 0 and 1000uS, it will be on for values higher than 1100uS. For values

between 1000uS and 1100uS the relay will be on or off depending on calculated percentage.

The calculation is based on a 100 seconds time. If Conductivity reaches 1030uS  the relay will be on

for 70 seconds and off for 30 seconds. To set the PROPORTIONAL functioning mode substitute

percentual value to “ON” and “OFF”.

It is not possible to enter mixed values (ex.: 100% for SP1 and ON for SP2). In this case it will not

possible save them.

In proportional mode the instrument  doesn’t show  % values for setpoints status but only if they

are on or off.

It is possible modify setpoint status  (on,off, %) and setpoint values  with RIGHT key on the function to

modify and using  “UP” and “DOWN” key to change the value. Enter the value and save by pressing

“E” to save.

Repeat sequence for setpoint 2 (OUT2).

Press “E” key to exit from setpoint setting. The display will show “SetPoint Saved” and it return

to the previous menu.

Out mA

This function allows to program the current output for driving a metering pump or a chart recorder.It is
possible to program in 0

÷

20mA mode or 4

÷

20mA mode in the working range between 0 and 2000uS.

The current output and the working range may be modified. Ex.: it is possible to set 4mA at 0uS and

20mA at 1000uS. In this case, if you connect a metering pump it will dose at the maximum flow at 0uS.

The pump will reduce the flow when Conductivity decrease and it will stop at 1000uS. If you connect

a chart recorder, a graphic curve will be printed. Use “UP” and “DOWN” keys to change these settings.

Press “RIGHT” key to scroll through the options. Press “E” to confirm.

Summary of Contents for DIN DIGITAL CD

Page 1: ...tant safety informations about installation and use of this equipment Ignoring this informations could result in injuries or damages It is strictly forbidden to use this equipment with radioactive che...

Page 2: ...authorized personnel only Always discharge the liquid end before servicing the instrument Empty and rinse the liquid end before work on a pump which has been used with hazardous or unknown chemicals A...

Page 3: ...AL WIRINGS 5 VIEW ON MENU 6 SETTING SETPOINTS 1 SETPN 6 Out mA 7 CALIBRATION 2 CALIB 8 DELAY 3 Delay 9 RESERVED 4 Reserv 9 PASSWORD SETUP 1 New Pw 10 MANUAL WORKING MODE 3 Serv 11 ERROR MESSAGES 11 Wa...

Page 4: ...selection Press RIGHT key for about 4 seconds to switch off the instrument the display shows OFF Repeat the sequence to return to the normal operating mode To reset the instrument restore default sett...

Page 5: ...Connect shield to ground 9 GND SEPR CONFIGURATION The instrument is set to work without a proximity sensor If needed proximity sensor turns the instrument into stand by mode if there isn t flow Instru...

Page 6: ...oll MAIN menu is configured as follows 1 Setup This menu is divided into 1 Setpn 2 Calib 3 Delay 2 Param This menu is divided into 1 New Pw 3 Serv service mode SETTING SETPOINTS 1 SETPN Out 1 and Out...

Page 7: ...de substitute percentual value to ON and OFF It is not possible to enter mixed values ex 100 for SP1 and ON for SP2 In this case it will not possible save them In proportional mode the instrument does...

Page 8: ...ment will show Comp 3 This is the temperature compensation coefficient Modify this value according with the table on the buffer solution chemical product bottle using UP and DOWN keys Press E to confi...

Page 9: ...aches the setpoint values Default value is set to 0 Select DELAY from SETUP menu The instrument will show OUT1 10 Sec Press RIGHT key The instrument will show OUT2 5 Sec Delay time can be set from 0 n...

Page 10: ...et Using UP or DOWN keys from Param menu choose 1 New Pw press E to confirm The display shows NEW PW 0 0 0 0 Use UP and DOWN keys to modify th first digit Use RIGHT key to go on the next digit Press E...

Page 11: ...ON is the status of N O contact closed and N C contact open OFF is the status of N O contact open and N C contact closed ERROR MESSAGES If the display shows an error message use the following table ER...

Page 12: ...on center for the recycling of electronic and electrical equipment For more information visit the online site When dismantling a pump please separate material types and send them according to local re...

Reviews: