background image

3.1.0.20 

Edition 02.11

Technical Information · GB

www.kromschroeder.com

•  Safe gas cleaning using filter pad and strainer
•  Easy installation into a system in conjunction with valVario valves and 

regulators

•  Installation in any position, even with optional pressure switch

Filter module VMF

Summary of Contents for Kromschroder VMF 110

Page 1: ...tion GB www kromschroeder com Safe gas cleaning using filter pad and strainer Easy installation into a system in conjunction with valVario valves and regulators Installation in any position even with optional pressure switch Filter module VMF ...

Page 2: ...atio control VCV and VMF fitted to a forced draught burner 4 1 1 3 Industrial burner with staged control 4 1 1 4 Industrial burner with continuous control 5 2 Function 6 3 Flow rate 7 3 1 Calculating the nominal size 7 4 Selection 8 4 1 Type code 8 5 Project planning information 9 5 1 Installation 9 6 Accessories 10 6 1 Seal set VA 1 3 10 6 2 Filter pad set 10 7 Technical data 11 7 1 Dimensions 12...

Page 3: ...ctors of the iron steel glass and ceramics industries and also in all areas of private and commercial heat generation It can easily be adapted to different pipes thanks to various flange shapes for the individual valVario valve sizes Its modu lar design allows assembly with valVario valves or regulators making it possible to construct space saving gas systems Forced draught gas burner with valVari...

Page 4: ... control the mixture setting is maintained over a wide control range while at the same time preventing air deficiency 1 1 3 Industrial burner with staged control VAG VBY BIC AKT IC 40 BVA M LEH EKO EKO VMV VMF VAS The high output impulse at the burner generated by this type of control produces a uniform temperature distribution and good circulation of the furnace or kiln atmosphere e g in heat tre...

Page 5: ...ream of the gas valve VAS and the air gas ratio control VAG is cleaned The gas air mixture is set using the fine adjusting valve VMV A constant mixture setting is maintained over a wide control range while at the same time preventing air deficiency This type of control is used on boilers with multi stage or infinitely adjustable forced draught burners Application Examples of application ...

Page 6: ...retaining frame with the filter pad is pulled out The retaining frame is opened and the filter pad can be taken out The VMF is delivered with two test points for pressure measure ment as standard The VMF can also optionally be delivered with two 1 8 screw plugs NO NC COM Base plate Retaining frame with strainer Filter pad Housing Pressure test point Pressure switch DG VC Flange VMF 1 to 4 with pre...

Page 7: ...ordance with the standards EN 13611 EN 161 This involves measuring the pressure 5 x DN upstream and downstream of the unit under test The pressure drop of the pipe is also measured but is not compensated for A pressure loss of 10 mbar must not be ex ceeded Reading instructions Should operating cubic metres V b have been used in the flow rate diagram instead of standard cubic metres V n then the pr...

Page 8: ...4 1 Type code Code Description VMF Filter module 1 2 Size 10 50 Without inlet flange Nominal inlet diameter 10 50 Without outlet flange Nominal outlet diameter R N F Rp internal thread NPT internal thread Flange to ISO 7005 05 pe max 500 mbar M P With pressure test points With screw plugs 1 2 3 4 With outlet pressure switch DG 17 VC DG 40 VC DG 110 VC DG 400 VC Specification omitted if the nominal...

Page 9: ...equired We recommend installation with the base plate pointing downwards or sideways so that dirt can be removed from the housing more easily Installation position when using valVario valves and regulators the VMF is fitted upstream of the valVario control The VMF can be installed as a standalone device in the pipe ...

Page 10: ...ock seal B 2 x O rings flange C 2 x O rings pressure switch D 2 x sealing rings test point 6 2 Filter pad set A B C D E Scope of delivery A 1 x retaining frame with strainer B 10 x filter pads C 10 x seals for the base plate D 2 x seals for 1 8 test points E 2 x screws for securing the base plate ...

Page 11: ...uest The gas must be dry in all conditions and must not contain condensate Max inlet pressure pe max 500 mbar 7 25 psig Ambient temperature 20 to 60 C 4 to 140 F no condensation permitted Storage temperature 20 to 40 C 4 to 104 F Housing aluminium Connection flanges with internal thread Rp to ISO 7 1 NPT to ANSI ASME with ISO flange DN 40 to ISO 7005 ...

Page 12: ...15 62 7 65 1 44 6 99 0 34 0 49 0 07 VMF 115 1 2 15 30 15 62 7 65 1 44 6 99 0 34 0 49 0 06 VMF 120 3 4 20 30 23 62 7 65 1 44 6 99 0 34 0 49 0 11 VMF 125 1 25 30 23 62 7 65 1 44 6 99 0 34 0 49 0 09 VMF 225 1 25 34 29 88 81 65 2 114 6 0 76 0 91 0 29 VMF 232 11 4 32 34 29 88 81 65 2 114 6 0 76 0 91 0 26 VMF 240 11 2 40 34 29 88 81 65 2 114 6 0 76 0 91 0 29 VMF 250 2 50 34 29 88 81 65 2 114 6 0 76 0 91...

Page 13: ... 1 08 0 15 VMF 115 1 2 15 1 18 0 59 2 46 2 56 1 76 3 89 0 75 1 08 0 14 VMF 120 3 4 20 1 18 0 91 2 46 2 56 1 76 3 89 0 75 1 08 0 23 VMF 125 1 25 1 18 0 91 2 46 2 56 1 76 3 89 0 75 1 08 0 20 VMF 225 1 25 1 34 1 14 3 46 3 19 2 57 4 51 1 66 2 01 0 64 VMF 232 11 4 32 1 34 1 14 3 46 3 19 2 57 4 51 1 66 2 01 0 57 VMF 240 11 2 40 1 34 1 14 3 46 3 19 2 57 4 51 1 66 2 01 0 65 VMF 250 2 50 1 34 1 14 3 46 3 1...

Page 14: ...1 F H3 H2 VMF 240 40F 1 4 Technical data Dimensions 7 1 3 VMF 240F Type Connection Dimensions Weight L1 F D H1 H2 H3 VMF F P VMF F M VMF F 1 4 Flange DN mm mm mm mm mm mm kg kg kg VMF 240 40 34 66 88 81 65 2 114 6 0 76 0 91 1 04 Without flanges and connection parts ...

Page 15: ...on 02 11 15 8 Maintenance Check for external tightness at least once per annum at least twice per annum for operation with biologically produced methane Replace filter pad as required see page 10 Filter pad set ...

Page 16: ...know the product To choose a product Planning To look for information My scope of functions Technical department Sales No answer Remarks Adobe Reader 7 or higher required Elster GmbH Postfach 2809 49018 Osnabrück Strotheweg 1 49504 Lotte Büren Germany T 49 541 1214 0 F 49 541 1214 370 info kromschroeder com www kromschroeder com www elster com The current addresses of our international agents are ...

Reviews: