5.3.1 Characteristics of fitting
• Minimum diameter 40 mm (1.57 in.);
•
Maximumradiusofcurvature300mm(0.98ft.);
• Minimum average slope of 45° with no siphons.
Ifthesecharacteristicscannotberespected,abasinmust
be placed at the bottom of the humidifier to collect water and
limescale (
p/n
VI
) (contact ELSTEAM’s sales office for more
information).
Features of basin
• Drainage pipe with siphon to collect limescale.
NOTICE
MALFUNCTIONING OF THE EQUIPMENT
Ifthewaterisharderthan40°f,thebasinmustbechecked
and cleaned at least twice a year.
Minima 45°
Fig. 4.
Drainage pipe
If the water hardness is the same as indicated in the section
"5.2.1 CHARACTERISTICS OF WATER" ON PAGE 13,
,thebasincanbe
cleaned once a year.
Ifthedrainagesystem-orthebasin-ismadeofanelectricallyconductivematerial,asasafetymeasureitmustbeconnected
to the earthing of the electrical system.
DANGER
RISK OF ELECTRIC SHOCK
Ifthebasinismadeofanelectricallyconductivematerial,eartheitherthebasinorthedrainagesystem.
Theoutletwatercanreachatemperatureof98°C(208.4°F)orhigher.
WARNING
RISK OF BURNS
•
Beforedrainingwater,makesureyouarewearingallthenecessarypersonalprotectiveequipment(PPE).
• Do not touch the equipment during draining.
5.4 Steam distribution in an AHU or duct
The humidifier must be connected to a stainless steel steam distributor with a fixing flange in engineering plastic in order to
distribute steam in the ventilation system.
The steam distributor must be installed:
• Vertically;
• At least one metre from the top of the duct;
• At the bottom of the duct (so the steam can mix properly with the air);
•
Higherthanthehumidifieroutlet;
•
Ascloseaspossibletothehumidifier(topreventreducedefficiency).
Thesectionoftheductwherethesteamdistributorisinstalledmustbeinsulated,waterproofandhaveadrainatthebottom.
The insulated pipe fitting between the humidifier and the distributor must not be fitted with siphons and must always slope
down towards the humidifier to ensure the condensate runs freely in the machine.
WARNING
MATERIAL DETERIORATION
• The special steam piping must be fixed to the boiler and stainless steel ramp with stainless steel ties.
• Only use material suitable for the intended use.