924KTE4.01 - KT
series humidifiers
05/2021
| 17 |
Description
Example
Installation example no. 4
Distributorisinstalledinahorizontalduct,positioned
lower than the humidifier.
Example of incorrect installation
Itisimportanttoavoidcondensationpocketsinthe
supply pipe.
5.4.3 Distributing steam in the room
A steam blower p/n ESR010700
mustbeinstalledifsteamistobedistributedintheroomwithoutusingventilationducts.For
moreinformation,visit
.
Thesteamblowermustbepositionedhorizontally,withthedistributionholesaimedupwards,atleastonemetrefromthe
ceiling and walls.
WARNING
RISK OF BURNS
The steam blower must be installed so it is accessible to qualified personnel only.
WARNING
HOT STEAM
Do not touch the equipment when it is in operation.
Itmustbepositionedatleastonemetrefromtheceiling(3.28ft.).
Steam blower power supply
Steam blowers:
• Single-phase 230 Vac models: Powered directly by the fuse holder.
• Three-phase models: Powered directly by the 230 Vac mains voltage.