Display
Description
Defines the inactive period of the evaporator fan while the compressor is
switched off.
Considerations
Fan cycle is the fan cycle on (
FC O
) time + the fan cycle off (
FC F
) time.
Range
1 to 30 minutes
Global default
0 minutes
20 minutes -
S Z
firmware
9.27
Display stability (d2)
The table below details the display stability (
d2
) parameter.
Display
Description
Defines the rate of change of the displayed temperature.
Limiting the rate of change provides a dampening effect so as not to concern
users should the air temperature rise quickly due to a door opening.
Increasing the value for the display stability (
d2
) slows the rate of change of the
displayed temperature.
Considerations
Use the global default value for normal operation.
Range
1 to 254
Global default
2
9.28
Buzzer enable (b0)
The table below detail the buzzer enable (
b0
) parameter.
Display
Description
Enables or disables a warning buzzer for alarm conditions.
Door open alarms always sound the warning buzzer.
Considerations
Following alarm conditions trigger the buzzer:
l
Refrigeration system failure (
rS F
)
l
Sensor failure (
PF1
,
PF2
, and
PF3
).
l
Gas cooler high temperature alarm
l
CO2 lock out alarm
l
Ht alarms
l
CO2 alarms - for ems CO2 firmware only
Door alarms sound the buzzer as standard.
Range
00 (disabled) or 01 (enabled)
Global default
01 (enabled)
75 of 86
27 February 2014