Display
Description
Prevents excessive condensation on the evaporator in environments where
warm, and presumed humid, air is present by operating the evaporator fan.
If the fan set point (
FS P
) temperature is exceeded, the evaporator fan runs
continuously even if the door is opened.
On reaching set point (
S P
) temperature, the evaporator fan switches off during
door openings.
Considerations
Not related to fan cycle on (
FC O
) or fan cycle off (
FC F
).
Not used on ems55
advanced
and ems55R
advanced
OFC
firmware
Range
01 to 30ºC (33 to 86ºF)
Global default
15ºC (59ºF)
9.13
Condenser high temperature (Ht)
The table below details the condenser high temperature (
Ht
) parameter.
Display
Description
Defines the maximum temperature measured in the refrigeration system by
monitoring the condenser sensor.
On reaching the condenser high temperature (
Ht
), the EMS controller disables
the compressor and activates an alarm.
Considerations
1. Is not used with CO2 (R744) coolers.
2. Requires a condenser sensor.
3. To set the condenser high temperature
(Ht
), measure the
refrigeration system temperature when the condenser is 75% blocked.
4. To disable, set below 50ºC or 122ºF.
Range
0.0 to 125ºC (32 to 257ºF)
Global default
0.0ºC (32ºF) - disabled.
9.14
Defrost activation temperature (ddt)
The table below details the defrost activation temperature (
ddt
) parameter.
Display
Description
Defines the temperature measured on the evaporator sensor that activates
an off-cycle defrost.
The defrost activation temperature minimizes the risk of evaporator icing up.
Considerations
Defrost method (
dF
) must be set to 1 to start defrost cycles on the defrost
activation temperature.
Available only with the ems55 series using
OFC
(
Open Front Cooler
) firmware
and the ems75sz.