60
Currents
As mentioned previously, after you have
Plugged in your Current Probes
recognized. Therefore, only minor configuration adjustments will need to be made in the
Current
Configuration Window.
Elspec supplies a complete range of Clamps with the Portable BLACKBOX
that are divided into two categories: Custom Clamps & all other Clamps - See
The Custom clamps are capable of measuring currents up to 3000 Amps at very high frequencies of
10 kHz. The probes provide a linear voltage output replicating input current waveform ranges of
either 30, 300, or 3000 Amperes. The Ampere setting is controlled & set by the user via a Rotary-
Switch. Due to the nature of this setting, the Hardware range needs to be configured accordingly in
the unit's Web Interface. As such, the configurations differ for the two different groups of Clamps -
Currents Configuration - Elspec Custom Clamps:
Access your Portable BLACKBOX Unit
Elspec's Web Interface
log on as the
Administrator
under
Configuration
Device Setup
select the
Currents Tab:
As mentioned all the connected clamps will be automatically recognized. Adjust the
Currents
Probe Info
in the applicable sections
:
Primary & Secondary Transformation Ratios
for all the Current channels;
Nominal Ampere Values
for all the Current Channels (Nominal is set for the current
measurements that will define PQZIP threshold / tolerance value & it is also used for event
settings);
Either
Reverse
the
Polarity
/ maintain it at
Normal
from the drop-down selection (Polarity
toggling is used to correct incorrect wiring);
Clamp’s
Current / Voltage Ratio
as per the
Clamp's Rotary Current Setting
- use the table
below as your guide:
CLAMP ROTARY CURRENT SETTING
I/V Ratio
30A
100 mVA
300A
10 mVA
3000A
1 mVA
Summary of Contents for G3500 BlackBox
Page 1: ...1 ...
Page 38: ...38 2Phase TR SINGLE SPLIT PHASE delta 3 wires THREE WIRE DELTA ...
Page 39: ...39 delta 3 wires Grounded Delta wye 4 wires four wire wye ...
Page 40: ...40 wye 4 wires three wire wye Delta 3 wires delta high leg ...
Page 82: ...82 The Average Window will now open ...
Page 96: ...96 The Waveforms Window will now open ...
Page 113: ...113 Export Dialog Various Export Options ...
Page 130: ...130 The window containing the table for V I Min Max Harmonics values will now open ...
Page 171: ...171 SEE ALSO About Energy Measurement Status ...
Page 207: ...207 SEE ALSO About the Current Window Current Probes Info Non Measured Currents ...
Page 217: ...217 Open the LAN Tab Select or complete the following in the applicable sections select ...
Page 220: ...220 You should now be able to identify the Router on your computer s Network Sharing Center ...
Page 247: ...247 ...
Page 327: ...327 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Page 331: ...331 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Page 334: ...334 SEE ALSO About Battery Replacement G3500 BLACKBOX Unit G4500 BLACKBOX Unit ...
Page 357: ...357 DIMENSIONAL VIEW G4500 ...
Page 358: ...DIMENSIONAL VIEW G3500 SEE ALSO G4500 G3500 Specifications ...