Setting of parameters
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
The behaviour with release of the switching output depends on the value of the para-
meter “Temperature switching output sends …” (see ”Temperature switching out-
put”)
4.13. CO2 PI control
Control general:
Controler target value:
If the target value is set per Parameter:
Value of parameter
„switching output sends“:
Setting options
„Behaviour of switching output with
release“:
on change
• do not send telegram
• send status of the switching output
on change to 1
• do not send telegram
• if switching output = 1
send 1
on change to 0
• do not send telegram
• if switching output = 0
send 0
on change and periodically
send status of the switching output
(no selection)
on change to 1 and periodically
if switching output = 1
send 1
(no selection)
on change to 0 and periodically
if switching output = 0
send 0
(no selection)
Use control
No • Yes
Type of control
• One-stage ventilation
• Two-stage ventilation
Behaviour of the blocking object with value
• 1 = block control | 0 = release control
• 0 = block control | 1 = release control
Value of the blocking object before
1. communication
0 • 1
Transmission behaviour of actuating
variables
• on change
• on change and periodically
Transmission cycle
(only if sending „periodically“)
5 s • 10 s • 30 s • 1 min • … • 2 h
Transmission behaviour of status objects
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Transmission cyle
(only if sending „periodically“ )
5 s • 10 s • 30 s • 1 min • … • 2 h
Target value setpoint per
Parameter • Communication object