28
Parameter setting
Actuator KNX S1R-BA4-UP 24 V
• Version: 27.05.2020 • Technical changes and errors excepted.
Block – wind blocking
The menu item only appears if a wind blocking was configured for "control". The input
object "wind blocking" is linked with the output object of a wind sensor. The input can
be a 1bit object (smaller or larger than a threshold value), as well as a 16bit object
(measurement value).
1 bit input object:
16 bit input object:
For manual operation before and after
blocking
• no action
• move into last position
For automatic operation after blocking
follow automatic
Value of the object before the 1st
communication and bus voltage return
0...1
Designation
[Wind blocking]
Enter a designation here!
Type of input object
1 bit • 16 bit
Type of input object
1 bit
If blocking object has value =1
• no action
• stop
• move into position
• up-command • down-command
(shutter/blind)
• retract-command • extend-command
(awning)
• close-command • open-command
(window)
Position in % (only if by using a block, a
specific position is achieved)
0...100
Slat position in % (only if by using a block,
a specific shutter position is achieved)
0...100
Waiting period in secure position in min
after blocking
1...255; 5
Behaviour after waiting period
For manual operation before and after
blocking
• no action
• move into last position
For automatic operation after blocking
follow automatic
Type of input object
16 bit
As of wind speed in m/s
blocking
2...30; 5