background image

Sensors Vari KNX 3L-T

1

Sensors Vari KNX 3L-T

 • Version: 06.12.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

Vari KNX 3L-T,

Vari KNX 3L-TH,

Vari KNX 3L-TH-D GPS

Combined brightness sensors

1.

Description

The 

Sensors Vari KNX 3L-T

 for the KNX building bus system record brightness

(sun), temperature and additionally air humidity and air pressure outside, depen-
ding on the model. The model Vari KNX 3L-TH-D GPS also receives the GPS signal
for time and location and uses it to compute the position of the sun (azimuth and
elevation).

The measurement values can be used for the control of limit-dependent switching
outputs. States can be linked via AND logic gates and OR logic gates. Multi-functi-
on modules change input data as required by means of calculations, querying a
condition, or converting the data point type.

All models have an integrated PI controller for heating/cooling. Models with humi-
dity sensor have a PI controller for ventilation.

The compact housing of the 

Vari KNX 3L

 accommodates the sensors, evaluation

circuits and bus-coupling electronics.

Functions of all models:

(70383 Vari KNX 3L-T, 70384 Vari KNX 3L-TH, 
70390 Vari KNX 3L-TH-D GPS)

Brightness measurement

: The current light intensity is measured by three 

sensors. Of the three measurement values, the maximum value or a 
calculated mixed value can be output optionally.

Switching outputs

 for all measured and computed values. Threshold 

values can be adjusted per parameter or via communication objects

8 AND and 8 OR logic gates

, each with 4 inputs. All switching events as 

well as 16 logic inputs (in the form of communications objects) can be used 
as inputs for the logic gates. The output of each gate can be configured 
optionally as 1-bit or 2 x 8-bit

8 multi-function modules

 (computers) for changing the input data by 

calculations, by querying a condition or by converting the data point type

Temperature measurement

 with 

mixed value calculation

. The share of 

internal measurement value and external value can be set as a percentage

PI-controller for heating

 (one or two-stage) and 

cooling

 (one or two-

stage) according to temperature. Regulation according to separate setpoints 
or basic setpoint temperature

Summer compensation

 for cooling systems. A characteristic curve 

matches the target temperature in the room to the external temperature and 
sets the minimum and maximum target temperature values

Additional functions of the models with humidity sensor:

(70384 Vari KNX 3L-TH, 70390 Vari KNX 3L-TH-D GPS)

Humidity measurement

 (relative, absolute), with 

Mixed value 

calculation

. The share of internal measurement value and external value 

can be set as a percentage. 
In addition the bus output will indicate whether the values are inside the 

comfort field

 (DIN 1946). The 

dewpoint

 will be calculated

PI controller for humidity

 according to humidity: Ventilate/Air (one-

stage) or Ventilate (one or two-stage) 

4 control variable comparators

 to output minimum, maximum or 

average values. 5 inputs each for values received via communication objects

Additional functions 70390 Vari KNX 3L-TH-D GPS:

Air pressure measurement: 

Output of the value as normal pressure and 

optionally as barometric pressure

GPS receiver

, outputting the current time and location coordinates. The 

Sensor Vari KNX 3L-TH-D GPS 

also computes the position of the sun 

(azimuth and elevation)

Configuration is made using the KNX software ETS. The 

product file

 can be dow-

nloaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the

“Service” menu.

1.0.1. Scope of delivery

Sensor

Stainless steel installation band for pole installation

4×50 mm stainless steel Roundhead screws and 6×30 mm dowels for wall 
mounting. Use fixing materials that are suitable for the base!

1.1. Technical specification

Vari KNX 3L-TH-D GPS:

Vari KNX 3L-TH:

Vari KNX 3L-T:

The product conforms with the provisions of EU directives.

2.

Installation and start-up

Installation, testing, operational start-up and troubleshooting should 
only be performed by an authorised electrician.

CAUTION!
Live voltage! 

There are unprotected live components inside the device.

• Inspect the device for damage before installation. Only put undamaged 
devices into operation. 
• Comply with the locally applicable directives, regulations and provisions 
for electrical installation. 
• Immediately take the device or system out of service and secure it against 
unintentional switch-on if risk-free operation is no longer guaranteed.

Use the device exclusively for building automation and observe the operating ins-
tructions. Improper use, modifications to the device or failure to observe the ope-
rating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.1. Installation location

Due to the GPS receiver, the Sensor 

Vari KNX 3L-TH-D GPS

 must be installed

outside. The 

other models

 can be mounted outside or inside.

The 

Vari KNX 3L-TH-D GPS and Vari KNX 3L-TH

 should be protected from

condensation. For critical applications in which the formation of condensation is
expected, please consult Elsner Elektronik about special solutions.

Select an installation position on the building where the sensors can measure
sunshine without any obstructions. The weather station should not be shaded by
structures or, for example, trees. Ensure no shadow is thrown on the device by an
extended awning.

Temperature measurements can also be distorted by external influences such as
warming or cooling of the building structure on which the sensor is mounted (sun-
light, heating or cold water pipes). Temperature variations from such sources of in-
terference must be corrected in the ETS in order to ensure the specified accuracy
of the sensor (temperature offset).

Note for devices with GPS receiver:

Magnetic fields, transmitters and interference fields from electrical consumers
(e.g. fluorescent lamps, neon signs, switch mode power supplies etc.) can block or
interfere with the reception of the GPS signal.

2.2. Device design

2.3. Installing the device

ATTENTION!

Even a few drops of water can damage the device electronics.

Do not open the device if water (e.g. rain) can get into it.

2.3.1. Preparation for installation

2.3.2. Fitting the lower part of the housing with mounting

Now, first of all, assemble the lower part of the housing with the integrated moun-
ting for wall or pole installation.

Technical specifications and installation instructions

Item numbers
70383 Vari KNX 3L-T
70384 Vari KNX 3L-TH
70390 Vari KNX 3L-TH-D GPS

Housing

Plastic

Colour

White / Translucent

Assembly

Surface mount

Protection category

IP 44

Dimensions

approx. 65 × 80 × 30 (W × H × D, mm)

Weight

approx. 60 g

Operating voltage

KNX bus voltage

Bus current

max. 20 mA

Data output

KNX +/- bus connector terminal

Group addresses

max. 2000

Assignments

max. 2000

Brightness sensor:
Measurement range

0 lux … 150,000 lux

Ambient temperature

Operation -25…+80°C, Storage -40…+85°C, 
avoid condensation

Communication 
objects:

603

Temperature sensor: 
Measurement range 

-25°C … +80°C

Humidity sensor:
Measurement range

0% RH … 100% RH

Pressure sensor:
Measurement range

300 mbar … 1100 mbar

Ambient temperature

Operation -25…+80°C, Storage -40…+85°C, 
avoid condensation

Communication 
objects:

421

Temperature sensor: 
Measurement range 

-25°C … +80°C

Humidity sensor:
Measurement range

0% RH … 100% RH

Ambient temperature

Operation -30…+50°C, Storage -30…+70°C

Communication 
objects:

339

Temperature sensor: 
Measurement range 

-30°C … +50°C

Fig. 1
The device must be attached to a ver-
tical wall (or a pole).

wall
or
pole

90°

Fig. 2
The device must be mounted in the 
horizontal (transverse) direction.

Horizontal

Fig. 3
For installation in the northern hemis-
phere, the device must be aligned to 
face south. 

For installation in the southern hemis-
phere, the device must be aligned to 
face north.

North

South

Wall/Pole

3

Fig. 4
1 Position of the brightness 

sensors 1-3. With align-
ment of the device to the 
south
Sensor 1 = West
Sensor 2 = South
Sensor 3 = East

2 Semi-transparent cover 

Vari KNX TH-D GPS: GPS 
receiver and pressure sen-
sor below.

3 Position of the Signal LED 

(under the cover). LED is 
freely controlled via two 
objects

4

8

7

1

5

2

6

1

3

2

4 Position of the programming LED (under the cover)
5 Lower part of housing 
6 Temperature and humidity sensor for Vari KNX 3L-TH-D GPS, Vari 

KNX 3L-TH.
Temperature sensor for Vari KNX 3L-T.

7 Programming key on the bottom of the housing (recessed), 

see 

Ad-

dressing the device

8 Wall/Pole holder

Fig. 5
The cover and lower part of the hou-
sing are connected together. Pull both 
parts apart in a straight line.

EN

Reviews: