Technical specifications and installation instructions

Item numbers 
TH PF-U: 40100 (white), 40101 (aluminium), 40102 (anthracite), 40103 (stainless steel)
TH PF: 40110 (white), 40111 (aluminium), 40112 (anthracite), 40113 (stainless steel)

TH PF
TH PF-U

Indoor Sensor and Ventilation Control

Summary of Contents for 40100

Page 1: ...0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de EN Technical specifications and installation instructions Item numbers TH PF U 40100 white 40101 aluminium 40102 anthracite 40103 stainless steel TH PF 40110 white 40111 aluminium 40112 anthracite 40113 stainless steel TH PF TH PF U Indoor Sensor and Ventilation Control ...

Page 2: ...different colours The Ventilation Controls TH PF U is equipped with two buttons for manual control of the respective window ventilator and for adjusting the device The display shows current measured values and mode and guides through the set up menus Functions Measuring the temperature and relative air humidity Control of a window of ventilator in one or two steps threshold values to be adjusted i...

Page 3: ... 40100 matt aluminium no 40101 matt anthracite no 40102 stainless steel no 40103 special colours on request Mounting Flush mounting wall mounting in junction box R 60 mm 42 mm depth Protection category IP 20 Dimensions Housing approx 55 x 55 W x H mm Mounting depth approx 15 mm Base plate approx 71 x 71 W x H mm Total weight approx 65 g Ambient temperature Operation 10 50 C storage 20 60 C Ambient...

Page 4: ...ed for its intended purpose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical damage If it has been damaged in transport inform the supplier immediately The device may only be used as a fixed site installation that means only when assembled and after concl...

Page 5: ...es and ducts which lead from warmer or colder areas to the sensor Measurement variations from such sources of interference must be corrected in the basic settings menu in order to ensure the specified accuracy of the sensor 2 3 Sensor connection and design 2 3 1 Housing 2 3 2 Connection board Fig 1 1 Base plate 2 Catches 3 Openings for air circulation 4 CLOSE button 5 CLOSE LED recessed 6 OPEN LED...

Page 6: ... Humidity 0 V 0 rF 10 V 100 rF white Temperature 0 V 10 C 10 V 50 C black GND together Fig 4 8 wire connecting cable for control outputs inputs and operating voltage blue Output 2 OPEN window Ventilator level 2 black Output 1 CLOSE window Ventilator level 1 purple Supply voltage for output 1 2 black Input 2 OPEN yellow Input 1 CLOSE black Supply voltage for input 1 2 white Operating voltage GND bl...

Page 7: ...nstallation and start up Ventilation Controls TH PF U Status 19 04 2016 Technical Changes and Errors excepted 2 3 3 Wiring diagrams Window Measuring value outputs only with model TH PF U Fig 5 With relays ...

Page 8: ...8 Installation and start up Ventilation Controls TH PF U Status 19 04 2016 Technical Changes and Errors excepted Measuring value outputs only with model TH PF U Fig 6 With Power Supply NG AQS TH PF ...

Page 9: ...lation and start up Ventilation Controls TH PF U Status 19 04 2016 Technical Changes and Errors excepted 2 3 4 Wiring diagrams Ventilation Units Measuring value outputs only with model TH PF U Fig 7 With Relays ...

Page 10: ...10 Installation and start up Ventilation Controls TH PF U Status 19 04 2016 Technical Changes and Errors excepted Measuring value outputs only with model TH PF U Fig 8 With Power Supply NG AQS TH PF ...

Page 11: ...he junction box and position the frame of the switch range on top of this Connect the operating voltage and all other connections Insert the sensor housing firmly into the metal frame using the catches so that the sensor and frame are fixed together 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not exceed a relati...