Brief Description / Applications

•  Controller for all kind of Storages, such as Walk-In Coolers/Freezers,    

  Refrigerated Shelfs, Refrigerated Counters, Refrigerated Cases, etc.

•  For standard cold storages or cold storages with pulse-width modulated 

  expansion valves, expansion valves with thermal drive and stepper 

  motor valves (with addtional EVS module)  

•  For single or network operation  

•  5 Temperature sensors, 5 Relays, 4 Digital Inputs, Analogue In-/Output

Please note safety instructions !

This is a brief version of the technical manual. 

A complete version you can find on www.elreha.de,  

our free INFO-CD and via Handy Apps.

Short Manual      

5321437-00/00

e

/00

Cold Storage  

2018-06-25, tkd/jr

Controller

 

 

 

 

Type:  

   

EVP 3167

ELEKTRONISCHE  REGELUNGEN  GMBH

LED on = cooling

LED blinking 

  = Min. idle time or  

  = Cooling delay after  

    mains failure

  = Cool. pause after defr.
LED on = defrost

LED blinking

  = Pause before defrost

LED on = fan is running

LED blinking

  = Start delay
Programming key

LED blinking = alarm

The currently displayed 

setpoint is active

increase 

values

decrease

values

3 keys allow programming the unit, all parameters will be displayed on 

the red LED-7-segment display. 4 red symbols at the right side indicate 

specific control functions (

not the relay states, these are displayed on the 

'Actual Page' !

).

DANGER

 CONNECTION INFORMATION & SAFETY INSTRUCTIONS

The guarantee will lapse in case of damage caused by failure 

to comply with these operating instructions! We shall not be 

liable for any consequent loss! We do not accept liability for 

personal injury or damage to property caused by inadequate 

handling or non-observance of the safety instructions! The 

guarantee will lapse in such cases. 

This  manual  contains  additional  safety  instructions  in  the 

functional description. Please note them!
If you notice any damage, the product may not be connected 

to mains voltage! Danger of Life!

A riskless operation is impossible if:

• The device has visible damages or doesn't work

• After a long-time storage under unfavourable conditions

• The device is strongly draggled or wet

• After inadequate shipping conditions

• Never use this product in equipment or systems that are  

  intended to be used under such circumstances that may  

  affect human life. For applications requiring extremely  

  high reliability, please contact the manufacturer first.

• 

The product may only be used for the applications  

  described above.

•  Electrical installation and putting into service must be  

  done from qualified personnel. 

• 

 During installation and wiring never work when the 

  electricity is not cut-off ! Danger of electric shock!

• 

To prevent electrical shock, the device may only be 

  operated in a closed control cabinet or control box.

• 

 Never operate unit without housing. 

  Danger of electric shock!

•  

All ‘PE’ terminals must be connected to PE.    

  Danger of electric shock! 

Additionally, the internal noise  

  filter will not work, faulty indicated values may occur.

•  Please note the safety instructions and standards of your  

  place of installation!
•  Before installation: Check the limits of the controller and  

  the application (see tech. data). Check amongst others:

  - Make sure that all wiring has been made in accordance  

    with the wiring diagram in this manual.

  - Supply voltage (is printed on the type label).

  - Environmental limits for temperature/humidity. 

  -  Maximum admitted current rate for the relays. Compare  

    it with the peak start-up currents of the controlled loads 

    (motors, heaters,etc.). 

 

  Outside these limits malfunction or damages may occur.

•  Sensor/probe cables must be shielded. Don’t install them  

  in parallel to high-current cables. Shielding must be  

  connected to PE at the end close to the controller. 

  If not, inductive interferences may occur. 

•  Please note for elongation: The wire gauge is not critical,  

  but should have 0,5mm² as a minimum.

•  Mounting the controller close to power relays is    

  unfavourable. Strong electro-magnetic interference,  

  malfunction may occur!

•  Take care that the wiring of interface lines meets the  

  necessary requirements.

•  TF-type sensors are not designed for being immersed in  

  fluids permanently. In such a case, always use dip-fittings.  

  With extreme temperature variations, the sensor may be  

  damaged.

Danger

Notice

 Technical Data

Supply Voltage .............................230V, 50-60Hz, max. 9VA (controller only)

Ambient Temperature .......................................................................0...+50°C

Max. Ambient Humidity ...........................................85% r.F., not condensing

Analogue Inputs   ........................... 5x Temperature Sensors TF 201 (PTC) 

 

 or TF 501 (Pt 1000), as well as customer specific probes

 

1x pressure transducer 0(2)-10V (scalable), Ri=69 kOhm

Measuring ranges ...................TF 501 

(Pt1000)

 .................... -100°C...+100°C  

of the probe inputs 

 

TF 201 

(PTC, 2 kΩ at°C)

 ........... -50°C...+100°C 

 

 

So1  ......................................... -40°C...+25°C 

 

 

So2  ......................................... -50°C...+50°C

 

 

TF 202 

(PTC, 990 Ω at 25°C)

 ..... -55°C...+100°C

 

The temperature ranges of the probe heads  

 

 

and cables must be observed !

 

Accuracy .....................................................±0.5K in range  -35...25°C within 

 

 

the ambient temperature range 10...30°C

Digital Inputs ......................................................4x mains voltage, 3mA max.  

 

 

overvoltage category  II, pollution degree 2

Relay Outputs .......................1x SPDT, 3x SPST, isolated, 8A res/3A ind./250V

 

 

overvoltage category  III, pollution degree 2

SSR-Output (e.g. for EEx-Valve) ...................... 1x Solid-State-Relay (SSR), 

 

 

max. 0,5 A / 250VAC  

 

 

overvoltage category  III, pollution degree 2

 

Please note the information at the connection plan about a 

 

necessary snubber circuit at the SSR output!

Transducer Supply .............................................22V DC ±10%, 40 mA max.

Analogue Output ...........................................0...10V or 4...20mA (selectable) 

 

 

0...10VDC, max. current typ. 1mA 

 

 

4...20 mA, max. shunt resistance 250 ohms

Display/Parameter Ranges .......................................... see parameter pages

Data Interfaces ...............................................................................3x RS 485

Data storage ......................................................................................unlimited

Real Time Clock ..........................................automatic summer/winter switch

 

 

10 days clock backup without mains voltage

Housing ................ plastic with foil keypad for rail mounting (DIN EN 50022),

 

 

screw terminals 2,5 mm