User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
36
If there is a problem with firmware update it will abort the process. To gain further
information on the updating process, connect to the RS232 port at 9600, n, 8, 1, and
you will see descriptive text on the progress and any error conditions that may be
reported.
Below is a guide to progress as observed from the Digital Input LEDs.
Digital Input Debug Digital Input LEDs
D1
Start Header Verification, Product ID Matched, Offset Matched, Entry/Destination
Address Matched, Firmware Length Matched, Polynomial Matched, CRC Matched,
Signature Length Matched
D2
OK (the signature is valid)
D3
Firmware updating....................100.00%
D4
Firmware update has been successful
Specifications
Operation
●
Modes / Topology: Remote Unit type.
Input and Output
●
Discrete Inputs/Outputs:
▪
Input:
▪
4 x digital I/O configurable as on/off or DI1 -3 pulse inputs
▪
On-state voltage: <2 Vdc
▪
Off-state voltage: >3 Vdc
▪
Wetting current: 30µA
▪
Minimum input pulse width 1ms (active input).
▪
Max Pulse Rate 10Hz
▪
Outputs
▪
ON/OFF or Latch (Drive H Bridge pulsed)
▪
ON current < 200mA
▪
OFF open circuit voltage < 30Vdc
▪
NPN Transistor close to ground when active
▪
Latch pulse time configurable in ms
●
Analog input:
▪
2 differential analog inputs configurable mA
▪
0-20mA current loop (under/over range)
▪
16 bits resolution
▪
Impedance < 250Ω
▪
Input/common mode voltage max 30Vdc
●
Sensor Loop Power:
▪
Analog: 24Vdc, max 50mA
▪
SDI-12 or Modbus: 12Vdc, max 500mA
●
Modbus RTU Smart Sensor
▪
Serial RS-485 communications with cable length less than 1km
▪
Maximum of 46 sensor variables in total for all slave devices
▪
Configurable serial baud rate (300-115,200), data bits, parity and stop bits
●
SDI-12 (V1.4):
▪
Maximum of 5 variables total: