Flow chart of parameter setting
In three-level state, if the parameter is not flashing, said the function code cannot be modified, possible reasons are:
The function code parameters can not be modified. Such as the actual testing parameters, operation records, etc.;
The function code in the running state cannot be modified, need to stop to modify;
3.3.2 Fault reset
After the failure of the inverter, the inverter will be prompted to related fault information. Users can press STOP key on the
keyboard or terminal function to conduct the fault reset (P5), after fault reset, the inverter is in the standby state. If the inverter
is in fault state, the user does not carry on the fault reset, the inverter is in the running to protect state, inverter can't run.
3.3.3 Motor parameter self-learning
1: The dynamic parameter self-learning
Choosing no PG vector control operation mode, input motor nameplate parameters must be accurate, inverter will based on
nameplate parameters matching standard motor; ln order to get better control performance, motor parameter auto-tuning is
suggested and auto-tuning steps are as follows:
First will run command channel choice (P2.00) choice for keyboard commands. Then the actual parameters according to the motor,
please input the following parameters.
P2.00: the motor type;
P2.01: the motor rated power;
P2.02: the motor rated voltage;
P2.03: the motor rated current;
P2.04: the motor rated frequency;