Summary of Contents for Fire Door Control Panel

Page 1: ...ire Door Control Panel FDCP Floats Rd Wythenshawe Manchester M23 9WB T 44 0 161 945 4561 F 44 0 161 945 4566 Stock Code Description Doc No PI 115 00133 00134 Ellard Fire Door Control Panel Ellard Slav...

Page 2: ......

Page 3: ...ton Connection 2 6 Key Switch Connection 2 7 Panic Button 2 8 Photo Beam 2 9 Relays 2 10 Solenoid Release Output 3 Motor Configuration Examples 3 1 230v AC Tubular Motors 3 2 24v d c Tubular Motors 3...

Page 4: ...g either board or box 180 and refitting see Fig 1 2 Mounting Mount the unit using the fixing holes provided see Fig 1 1 BOTTOM CABLE ENTRY A A A A Fig 1 1 Enclosure Mounting TOP CABLE ENTRY Fig 1 2 Ca...

Page 5: ...n and to operated a 24v brake release device in the even of a power failure Select able fire signal Normally Open N O or Normally Closed N C volt free potential Dry contact or 2 30V d c direct input L...

Page 6: ...fitted across input connections Normally Close N C Triggers the panel by a N C volt free signal which OPENS when the fire alarm is activated 24v d c Triggers the panel by removing a permanently connec...

Page 7: ...her relays or switch upon Low Battery power or Mains Fail N O not used 2 10 24v d c Solenoid Output A brake release device or solenoid unit can be activated when connected to the output provided This...

Page 8: ...EE PROGRA MMING INSTRUCTION CONSIDERATION MUST B E TAKEN F OR THIS CONFIGURA TION DOOR WILL ONLY RUN PROVID ING 230V AC MAINS SUPPLY IS AVAILAB LE A SUITAB LE BATT ER Y BACK UP THEREFORE MAY NEED PROV...

Page 9: ...R OPEN SEE PROGRA MMING INSTRUCTION CONSIDERATION MUST B E TAKEN F OR THIS CONFIGURA TION DOOR WILL ONLY RUN PROVID ING 230V AC MAINS SUPPLY IS AVAILAB LE A SUITAB LE BATT ER Y BACK UP THEREFORE MAY N...

Page 10: ...MUST BE INSTALLED FOR 1 PHASE OPERATORS THE MOTOR SUPPLY CAN BE SUPPLIED VIA AN INDEPENDENT SUPPLY OR TAKEN DIRECTLY FROM TERMINAL TS3 PE L N 3 3 Connection for JM series motors fitted with 24V DC bra...

Page 11: ...CAN BE CONNECTED TO AN INDEPENDENT SUPPLY FITTED WITH SUITABLE FUSE PROTECTION OR TAKEN DIRECTLY FROM TERMINAL TS3 PE L N 3 4 Connection for other motors with built on controllers Use with Power Clos...

Page 12: ...ctivation shutter descends to full closed position TS6 7 8 9 10 11 12 NC com NO AUX1 NC com NO AUX2 4 Typical Connection for RELAY BASE Stand Alone Heat and Smoke Detectors Relay Base Supplier Apollo...

Page 13: ...part close position 1st Stage Program Choice 2 Stage Closing 2nd stage activation using a Smoke Heat Detector with Relay Base Signal Shown Normally Open N O COM N O COM 8k2 RESISTOR Used as Local Fire...

Page 14: ...LOSE PAUSE Only available if 2 stage closing selected This is the pause time after the shutter has driven to its first stage The Audio Visual will continue until receipt of a second or continuing sign...

Page 15: ...EOPEN TIME If the photo beam remains blocked another attempt will be made to close the shutter this will continue for the selected number of times If the obstruction is removed before this count is re...

Page 16: ...FDCP Repeater Panel is designed so the cable entry can be via the top or bottom of the panel by means of removing the PCB fixing screws then rotating either board or box 180 and re fitting see Fig 1...

Page 17: ...6 1 Connection detail for repeater panel...

Page 18: ...ow Check if mains supply is ok Batt test failed Replace batt Battery load is tested 1 5 sec 2mins after power up and then each 12 hours Check if battery is connected before powering up Battery has det...

Page 19: ......

Page 20: ......