70
MP500/4N-8-16 Installation
5.7
INSTALLATION OF THE EP508 EXPANSION
In addition to inside the control panel, the EP508 expansion can also be installed inside a CP/EXP container (certified Grade 3) or a
CP/EP500 container (not certified).
IMPORTANT!
the absence of a casing certified Grade 2 or 3 results in the loss of certification.
The tamper of the container must be connected to the SAB of the expansion.
The expansion has terminals for connecting the power supply, detectors, ad signalling devices, etc.
The electric outputs can be transformed into relay outputs
Figure 45 - EP508 Expansion
Detail
Terminal /
Detail
Description
A
+
BUS Expansion unit power input via bus
+D
BUS Data transmission / reception
D
─
BUS Expansion unit power input via bus
B
+V1
Power supply for output actuators (13.2 V
⎓
limited to 500 mA)
-V1
NC1
Relay output 1
– contact normally closed
NO1
Relay output 1
– contact normally open
C1
Relay output 1
– common (max. 1 A - 24 V
⎓
)
U2
Electric output 2 (current protected max. 10 mA)
U3
Electric output 3 (current protected max. 10 mA)
C
+V2
-V2
Power to detectors connected to expansion unit (13.2 V
⎓
limited to 500 mA).
Four pairs of power terminals are connected to the expansion unit.
IN1
Alarm input n. 1
IN2
Alarm input n. 2
IN3
Alarm input n. 3
IN4
Alarm input n. 4
IN5
Alarm input n. 5
IN6
Alarm input n. 6
IN7
Alarm input n. 7
IN8
Alarm input n. 8
D
SAB
Input 24h (for system self-protection). It must always be BALANCED and closed with a 15
kΩ
balancing resistor
E
Button
Yellow
LED
Device acquisition button and LED
F
RUN
Green LED signals operating (for details see the
Programming Manual
)
Slow blinking
= normal operating conditions
Fast blinking
= no communication with control panel for at least 1 minute
For details on connections (power supplies, inputs, outputs, bus, etc. …) see paragraph
and
paragraphs,