C420 Programming Manual
By pressing the DOWN key, the screen with the current settings of the parameters is displayed (only the parameters related
to the current programming mode are shown):
By pressing UP, the previous screen is shown; by pressing DOWN once again, the following screen with the association of the
zone relay to the triggering condition is displayed:
UP/DOWN keys are used to go back and forth through the screens. By pressing LEFT or MENU/ESC the previous menu is shown.
3.2.4 Outputs and Relays
By selecting this item, the following menu is shown:
3.2.4.1
Siren output
By selecting
‹‹
SIREN OUTPUT
››
, the correspondent inclusion/exclusion menu is shown (when the menu is entered, the selector
selects the currently active option):
3.2.4.2
Programmable relay
By selecting
‹‹
PROGRAMMABLE RELAY
››
, the following menu is shown:
The programmable relay can be programmed to signal the presence of exclusions or the lack of AC mains.
The selector position when the menu is entered indicates the current programming option of the relay.
By selecting
‹‹
NO AC POWER
››
and confirming the selected choice by pressing the RIGHT key, the currently programmed
activation delay is shown and the user can edit its value (range 0
– 10 minutes):
If the AC mains is missing, the relay will be activated when the delay programmed through this menu expires.
DELAY: XX
MASTER ALARM: YES/NO
ALARM CONFIRMATION (EN54-2 7.12.1): YES/NO
RELAY ACTIVE FOR
ALARM WITH OUTPUT SIREN ACTIVE
> SIREN OUTPUT
PROGRAMMABLE RELAY
SUPPLEMENTARY SIREN OUTPUTS
SIREN OUTPUT
> INCLUDED
EXCLUDED
PROGRAMMABLE RELAY
> EXCLUSIONS
NO AC POWER
PROGRAMMBLE RELAY
NO AC POWER
DELAY: __