background image

ELK-319HRR Heat & Rate of Rise Sensor

Description

The ELK-319HRR is a Supervised, Wireless Heat Sensor.  It 

uses a solid-state thermistor to sample and trigger an event 

at a selectable setpoint of either 135 or 200 degrees F.  It can 

also trigger an event if the temperature rises 12 degrees F or 

more during a one (1) minute time period.  

When an event is triggered the sensor transmits an alarm (trip) 

signal to the panel. Additionally transmitted signals include: 

tamper, hourly supervisory, and low battery (as needed). The 

sensor is powered by a single 3V lithium battery which can 

provide up to 10 years of life.

This sensor is compatible with Elk’s 319MHz Receivers/Panels 

as well as many other panels that operate on the 319.5MHz 

Frequency and adhere to the ITI/Interlogix protocol.  

Specifications

RF frequency:  319.5 MHz 
Supervision

Interval: 

62 - 68 minutes

Compatibility:  ELK-319 Receivers/Panels & other panels  

 

that operate on the 319.5MHz Freq. and 

   

adhere to the ITI/Interlogix protocol 

Battery type:   One (1) 3VDC lithium battery (Panasonic or 

   

Varta Model CR123)  Exp. Battery life 10 yrs

Rate of Rise

Rating: 

12° to 15°F (6.7° to 8.3°C)

UL max. 

Ambient ceiling: 100°F/150°F (37.8°C/65.6°C
Maximum

UL Spacing:  50ft (15.2m) x 50ft (15.2m)
Storage

Temp Range:   -30 to 167°F (-34 to 75°C) 
Relative

Humidity:  

0 to 95% non-condensing 

Dimensions      2.29” Dia. x 1.28” H  (58.25mm x 32.4mm)

Programming (Enrollment)

The following is a general guideline for programming (enrolling) 

a sensor into the receiver or panel. For more extensive 

instructions please refer to the receiver or panel instructions. 
1.  Place the panel into the Program mode. 
2.  Proceed to the WIRELESS SETUP menu. 
3.  Select the appropriate zone/sensor location number. 
4.  When prompted by the panel to trip the sensor for learning: 
•  Remove the battery pull tab which will power up the sensor
•  The panel should acknowledge the sensor has been learned 

by keypad display and/or audio alert (depending on the 

panel).  If enrollment fails try pressing and releasing the 

tamper plunger.  In some cases it may be necessary to 

remove and reinstall the batteries.

5.  Repeat the above process for any additional wireless 

sensors.  Proceed to the zone programming to assign each 

sensor’s zone definition.  

6.  Exit programming mode when finished.

Installation Guidelines

•  Operation should be tested from the desired location to 

make certain it can be received by the panel before drilling 

any holes or permanently mounting the sensor 

•  Mounting  this  sensor  on  metal  can  negatively  affect  the 

transmitting range. 

•  Install the sensor within 100 ft. of the receiver or panel.
•  Heat sensors such as this are recommended for areas 

like garages, kitchens, attics, utility & equipment closets or 

places where a smoke detector is not advisable.

•  Avoid areas that may experience extreme or rapid increasing 

temperatures such as near: fireplaces, stoves, heaters, etc.

•  Mount this sensor on ceilings at least 4 inches away from 

any wall.  If placed on a wall the sensor must be within 6 

inches of the ceiling.

•  If using the 135°F setting make sure the ceiling location 

does not exceed this temperature.

TM

  Interlogix is a registered trademark belonging to United Technologies.

Setup

The sensor can be setup to detect a fixed temperature of either 

Low (135°F) or High (200°F).
Use the jumper to select Low or Hi.

Fixed Temperature
Low = 135°F
High = 200°F
Note: If no jumper is installed 

the sensor will be set to 200°F.

Reviews: