ELK-319HRR Heat & Rate of Rise Sensor
Description
The ELK-319HRR is a Supervised, Wireless Heat Sensor. It
uses a solid-state thermistor to sample and trigger an event
at a selectable setpoint of either 135 or 200 degrees F. It can
also trigger an event if the temperature rises 12 degrees F or
more during a one (1) minute time period.
When an event is triggered the sensor transmits an alarm (trip)
signal to the panel. Additionally transmitted signals include:
tamper, hourly supervisory, and low battery (as needed). The
sensor is powered by a single 3V lithium battery which can
provide up to 10 years of life.
This sensor is compatible with Elk’s 319MHz Receivers/Panels
as well as many other panels that operate on the 319.5MHz
Frequency and adhere to the ITI/Interlogix protocol.
Specifications
RF frequency: 319.5 MHz
Supervision
Interval:
62 - 68 minutes
Compatibility: ELK-319 Receivers/Panels & other panels
that operate on the 319.5MHz Freq. and
adhere to the ITI/Interlogix protocol
Battery type: One (1) 3VDC lithium battery (Panasonic or
Varta Model CR123) Exp. Battery life 10 yrs
Rate of Rise
Rating:
12° to 15°F (6.7° to 8.3°C)
UL max.
Ambient ceiling: 100°F/150°F (37.8°C/65.6°C
Maximum
UL Spacing: 50ft (15.2m) x 50ft (15.2m)
Storage
Temp Range: -30 to 167°F (-34 to 75°C)
Relative
Humidity:
0 to 95% non-condensing
Dimensions 2.29” Dia. x 1.28” H (58.25mm x 32.4mm)
Programming (Enrollment)
The following is a general guideline for programming (enrolling)
a sensor into the receiver or panel. For more extensive
instructions please refer to the receiver or panel instructions.
1. Place the panel into the Program mode.
2. Proceed to the WIRELESS SETUP menu.
3. Select the appropriate zone/sensor location number.
4. When prompted by the panel to trip the sensor for learning:
• Remove the battery pull tab which will power up the sensor
• The panel should acknowledge the sensor has been learned
by keypad display and/or audio alert (depending on the
panel). If enrollment fails try pressing and releasing the
tamper plunger. In some cases it may be necessary to
remove and reinstall the batteries.
5. Repeat the above process for any additional wireless
sensors. Proceed to the zone programming to assign each
sensor’s zone definition.
6. Exit programming mode when finished.
Installation Guidelines
• Operation should be tested from the desired location to
make certain it can be received by the panel before drilling
any holes or permanently mounting the sensor
• Mounting this sensor on metal can negatively affect the
transmitting range.
• Install the sensor within 100 ft. of the receiver or panel.
• Heat sensors such as this are recommended for areas
like garages, kitchens, attics, utility & equipment closets or
places where a smoke detector is not advisable.
• Avoid areas that may experience extreme or rapid increasing
temperatures such as near: fireplaces, stoves, heaters, etc.
• Mount this sensor on ceilings at least 4 inches away from
any wall. If placed on a wall the sensor must be within 6
inches of the ceiling.
• If using the 135°F setting make sure the ceiling location
does not exceed this temperature.
TM
Interlogix is a registered trademark belonging to United Technologies.
Setup
The sensor can be setup to detect a fixed temperature of either
Low (135°F) or High (200°F).
Use the jumper to select Low or Hi.
Fixed Temperature
Low = 135°F
High = 200°F
Note: If no jumper is installed
the sensor will be set to 200°F.