SPECIFICATIONS
Model EL250
EL1000
Output Rating @ 230V (VA)
250
1000
Output Current Rating (Amps)
1.1
4.35
Input Voltage (VAC)
200-240
200-240
Input Frequency (Hz)
50-60
50-60
Operating Temperature
0-30
0-30
(non-condensing) °C
Output Voltage (VAC)
As Input
As Input
Load Regulation
±3%
±1,5%
Inrush Capacity – ½ cycle (Amps)
35
150
Inrush Capacity – 1 sec (Amps)
9
25
Inrush Capacity – 10 secs (Amps)
5
17
Forward Transfer Impedance @ 1kHz
25
Ω
11
Ω
Output Current Crest Factor for 10% (max) drop in peak voltage
3
3
Efficiency at 80% load
92%
95%
Earth Leakage Current (typical) (µA)
50
75
50-ohm Attenuation
Normal-Mode 100kHz
60dB
60dB
Normal-Mode 30kHz-30MHz
>40dB
>40dB
Common-Mode 0-1MHz
>60dB
>60dB
Common-Mode 0-30MHz
>30dB
>30dB
0.1µs/100kHz 6kV Ring-Wave attenuation NM
< 6V
< 6V
0.1µs/100kHz 6kV Ring-Wave attenuation CM
< 1V
< 1V
Ground-Watch ® Impedance
>500
Ω
>500
Ω
10KHz-10MHz
Output receptacle type
IEC320
IEC320
Number of Output Receptacles
1
4
Size w x d x h (mm)
222x160x130
306x230x180
Wall-mount screw spacing (mm)
120
190
Weight (net) (kg)
5.25
19
Fuse 20x5mm HBC (ceramic) Type T
3.15A
10A
© Elinex Power Solutions b.v.
www.elinex.com
3516 Iss 5
The Elinex Low Impedance AC Power Conditioner provides
super-clean electrical power to sensitive electronic
equipment. Unlike ordinary power conditioners, its
low transfer impedance does not restrict the harmonic
currents taken by modern switchmode power supplies,
and its low output impedance does not magnify the
levels
exported
noise always present in your own
equipment. It is capable of supplying the full inrush
and surge currents taken by many types of equipment
and therefore does not have to be de-rated for some
applications. Unlike ordinary power-line filters, its wide
bandwidth and non-saturable magnetic characteristics
ensure effective elimination of noise and transient
surges across the entire spectrum, and up to 6 kilovolts
in amplitude.
The Elinex AC Power Conditioner provides a special
“Local Clean Earth” independent of the signal quality of
the building’s electrical safety earth system.
www.elinex.com
Low Impedance
POWER CONDITIONER
USER INSTRUCTIONS
ELX_manual_148x210mm.indd 1-2
ELX_manual_148x210mm.indd 1-2
13-02-2009 15:39:37