3.3 Parameter overview
The following parameters are available. Not all paramters can be changed. Parameters which can not
be changed are marked with a * and are read only. Most parameters which can not be changed are
for measurements only.
Parameter 4 and 9 are used for the power calculations. Parameter 4 holds the secundairy value of
the CT and parameter 9 the primairy.
Number Description
Default
Minimum value
Maximum value Symbol
P1
Generator power*
0
0
999
kW
P2
CT current*
0
0
1
–
5
A
P3
CT current in % of maximum
0
0
100
%
P4
CT type (1A
–
5A)
1
1
5
A
P5
Minimum setpoint generator
50
0
100
%
P6
Ramp up speed
30
0
60
Seconds
P7
Ramp down speed
5
0
60
Seconds
P8
Power correction
1
0.00
2.00
P9
CT ratio (P4:P9)
100
1
1000
A
P10
Output type
1
1
5
See table
3.4 Output selection type
The 4 relays on the controller can be programmed with different functionality. There are 3 main
output modes, the BAR mode, the DOT mode and the BINAIR mode each having the possibility to set
a minimum value rather than having all the relays off.
When the time set with P7 is elapsed, the next output type is selected. When the value is below 0 %
either no output will be selected (without minimum) or the lowest possible value is selected (with
minimum).
Parameter 10
Mode
Limitation
Relay output
1
2
3
4
1
BAR without minimum
0 %
X
30 %
X
X
60 %
X
X
X
100 %
X
X
X
X
2
BAR with minimum after
delay of P7
0 %
X
0 %
X
X
30 %
X
X
X
60 %
X
X
X
X
100 %
X
X
X
X