REGENERATIVE
SINUS PENTA
APPLICATION
68/
140
0
1
2
3
4
2.10.
COMMISSIONING
2.10.1.
C
OMMISSIONING OF THE
D
RIVE
U
SED AS A
R
EGENERATIVE
F
EEDER
The SINUS PENTA for the regenerative application is factory-set as follows:
Drive Class
Rated Voltage
(C500)
Rated Frequency
(C501)
2T 230.0
V 50
Hz
4T 400.0
V 50
Hz
5T 575.0
V 50
Hz
6T 690.0
V 50
Hz
Table 1: Default values of parameters C500 and C501 (electric mains).
For different rated voltage/frequency values, parameters concerning the electric mains must be set up before
activating the drive.
For optimum performance, also adjust parameterization of the drive controlling the motor by setting the Rated
Mains Voltage parameter (C008 for the Sinus Penta) to xT Regen, where “x” is the voltage class of the drive
being used.
1) Wiring:
Follow the instructions given in the sections of this manual covering the drive wiring
diagrams.
CAUTION Wrong wiring can cause the equipment malfunction.
2) Power on:
Power on the drive; the link to the ENABLE input (terminal 15) is to be open, so that the
drive is disabled.
Make sure that the drive is set up for the regenerative application: this is shown on the
start page (see below; line 1 states that the regenerative unit is waiting for the Enable
signal) or on the product ID screen in the IDP menu.
R E G E N . W A I T E N A
M 5 0 5 = +
0 . 1 k W
M 5 0 2 = 4 0 9 . 2 V
[ M E A ] P A R C F I D P
NOTE
When the regenerative drive is powered on, the motor drive powers on as well.
Parameters can be changed for both drives.