RIGENERATIVE
SINUS PENTA
APPLICATION
122/
140
0
1
2
3
4
0
1
2
3
4
3.12.2.
L
IST OF
P
ROGRAMMABLE
P
ARAMETERS
C500
TO
C503
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
C500
Rated Mains Voltage
BASIC 1000
Depending on
voltage class
C501
Rated Mains Frequency
BASIC 1001 50.0
Hz
C502
Mains Fault Enable
ENGINEERING
1002 1:
Yes
C503
Motor Drive Enabling Mode
ADVANCED 1003 2:REGEN
RUN
Table 18: List of Parameters C500 to C503.
C500 Rated Mains Voltage
C500
Range
2T Class
→
2000
÷
2400
4T Class
→
3800
÷
4800
5T Class
→
5000
÷
6000
6T Class
→
6000
÷
6900
2T Class
→
200.0
÷
240.0 V
4T Class
→
380.0
÷
480.0 V
5T Class
→
500.0
÷
600.0 V
6T Class
→
600.0
÷
690.0 V
Default
2T Class
→
2300
4T Class
→
4000
5T Class
→
5750
6T Class
→
6900
2T Class
→
230.0 V
4T Class
→
400.0 V
5T Class
→
575.0 V
6T Class
→
690.0 V
Level
BASIC
Address
1000
Function
This parameter sets the rated mains voltage used to calculate
the trip thresholds of the mains alarms that can be set through
the parameters included in the Mains Monitor menu (P550,
etc.).
C501 Rated Mains Frequency
C501
Range
400
÷
700
40.0
÷
70.0 Hz
Default
500
50.0 Hz
Level
BASIC
Address
1001
Function
This parameter sets the rated mains frequency used to calculate the
min./max. frequency thresholds set through parameters P562 and P566 in
the Mains Monitor menu.