ELEQ LS-94 Installation Manual Download Page 1

 

 

Technical Specification 

 

Safety and environmental conditions 

CE marking 

 

 

LV directive 2006/95/EC 

RoHS directive  2011/65/EU 

WEEE directive 2012/19/EU 

Standard

 

EN-IEC 61439-2:2011 

EN-IEC 60269-3:2013 

 

This product is designed to be safe under the following 

conditions: 

 

Specification 

Environmental conditions 

Operating temperature: 

Relative humidity: 

Protection degree: 

Installation class: 

Pollution degree: 

 

-5°C - +55°C 

5% - 85%, non condensing 

IP23 

1 (protective earth) 

Application conditions 

Umax: 

Frequency: 

Imax:    

Fuse: 

Strain relief: 

 

Maximum wire cross section 

and torque: 

 

 

 

Diameter ø  

Height  

 

230V (L-N) 

50Hz 

25A (mantle terminals) 

1x DII (E27), max 6A 

Yes, maximum 2 ground cables 

23mm and 2 light poles cords 

 

Terminal N, 1, 2, 3: 2x 10mm

2

, 2-

4Nm 

Terminal 4, 5: 2,5mm

, 1-2Nm 

Terminal 6, 7: 1,5mm

2

, spring 

94mm 

279,5mm 

Storage 

Temperature: 

Relative humidity: 

 

-20°C - +70°C 

5% - 85%, non condensing 

Approval 

 

Specification per type 

 

5L2411 

Fuse included 

No 

Phase selection 

Yes 

PE-N connection 

No 

Covered mantle 

terminals 

Yes 

Weight 

597gr 

Surge Protection 

Device (SPD) 

Citel MLPC1-230L-R* 

Protection level 10kA/10kV  

Spring terminal connection for max 1,5mm² 

*

 Please consult www.citel.fr for more information about the MLPC1- 230L-R

 

 

 

 

Please be aware, product liability, fulfilment to requirements and 

warranty are all expired when modifications on the product are made. 

 

ELEQ reserves the right to carry out modifications on its products, in 

order to improve them, without prior notice.  

Safety instruction 

All activities for installation, commissioning and maintenance of 

this connection box must be performed by qualified personnel 

that has the knowledge of applicable safety precautions. This 

guide assumes that the reader of this document has sufficient 

electro-technical knowledge to understand the content of this 

document. 

 

General 

The LS-94 is a connection box for public lighting and intended 

to  be used in lighting poles.  The connection box shall  be 

mounted in a weather protected and dry location. In the 

connection box the incoming (ground) cable can be connected. 

If desired, looped circuits wiring  to the next lighting pole is 

possible. The cable of the armature shall be connected on the 

outgoing terminals. 

 

Fuses protect the installation against overload  and short-

circuiting.  

 

Explanation of symbols 

 

This product is designed according to the 

EN-IEC 61439-2:2011  standards and meets the 

requirements of the Low Voltage Directive 2006/95/EC. 

 

 

Read the installation guide before mounting the 

product. Unprofessional work activities on electrical 

installations may result in a threat of danger to the life 

and health of human beings and livestock! 

 

 

RoHS Directive 2011/65/EU 

ELEQ states that it uses qualified components in its 

products only from manufacturers which meet the 

requirements of the European Directive for the 

"Restriction of use of certain Hazardous Substances 

 

 

WEEE Directive 2012/19/EU 

This  equipment should not be disposed as unsorted 

municipal waste. Contact a qualified recycler for 

disposal. 

 

 

 

 

 

 

 

 

 

 

 

LS-94 Connection Box for  

Public Lighting 

Installation Guide 

 

 

 

                    

 

 

 

 

 

 

LS-94   

 

5L2411 

 

 

 

 

 

Read this installation guide before installing the product 

 

 

 

 

 

 

83751 

/ EN1603

 

 

 

Technical Specification 

 

Safety and environmental conditions 

CE marking 

 

 

LV directive 2006/95/EC 

RoHS directive  2011/65/EU 

WEEE directive 2012/19/EU 

Standard

 

EN-IEC 61439-2:2011 

EN-IEC 60269-3:2013 

 

This product is designed to be safe under the following 

conditions: 

 

Specification 

Environmental conditions 

Operating temperature: 

Relative humidity: 

Protection degree: 

Installation class: 

Pollution degree: 

 

-5°C - +55°C 

5% - 85%, non condensing 

IP23 

1 (protective earth) 

Application conditions 

Umax: 

Frequency: 

Imax:    

Fuse: 

Strain relief: 

 

Maximum wire cross section 

and torque: 

 

 

 

Diameter ø  

Height  

 

230V (L-N) 

50Hz 

25A (mantle terminals) 

1x DII (E27), max 6A 

Yes, maximum 2 ground cables 

23mm and 2 light poles cords 

 

Terminal N, 1, 2, 3: 2x 10mm

2

, 2-

4Nm 

Terminal 4, 5: 2,5mm

, 1-2Nm 

Terminal 6, 7: 1,5mm

2

, spring 

94mm 

279,5mm 

Storage 

Temperature: 

Relative humidity: 

 

-20°C - +70°C 

5% - 85%, non condensing 

Approval 

 

Specification per type 

 

5L2411 

Fuse included 

No 

Phase selection 

Yes 

PE-N connection 

No 

Covered mantle 

terminals 

Yes 

Weight 

597gr 

Surge Protection 

Device (SPD) 

Citel MLPC1-230L-R* 

Protection level 10kA/10kV  

Spring terminal connection for max 1,5mm² 

*

 Please consult www.citel.fr for more information about the MLPC1- 230L-R

 

 

 

 

Please be aware, product liability, fulfilment to requirements and 

warranty are all expired when modifications on the product are made. 

 

ELEQ reserves the right to carry out modifications on its products, in 

order to improve them, without prior notice.  

Safety instruction 

All activities for installation, commissioning and maintenance of 

this connection box must be performed by qualified personnel 

that has the knowledge of applicable safety precautions. This 

guide assumes that the reader of this document has sufficient 

electro-technical knowledge to understand the content of this 

document. 

 

General 

The LS-94 is a connection box for public lighting and intended 

to  be used in lighting poles.  The connection box shall  be 

mounted in a weather protected and dry location. In the 

connection box the incoming (ground) cable can be connected. 

If desired, looped circuits wiring  to the next lighting pole is 

possible. The cable of the armature shall be connected on the 

outgoing terminals. 

 

Fuses protect the installation against overload  and short-

circuiting.  

 

Explanation of symbols 

 

This product is designed according to the 

EN-IEC 61439-2:2011  standards and meets the 

requirements of the Low Voltage Directive 2006/95/EC. 

 

 

Read the installation guide before mounting the 

product. Unprofessional work activities on electrical 

installations may result in a threat of danger to the life 

and health of human beings and livestock! 

 

 

RoHS Directive 2011/65/EU 

ELEQ states that it uses qualified components in its 

products only from manufacturers which meet the 

requirements of the European Directive for the 

"Restriction of use of certain Hazardous Substances 

 

 

WEEE Directive 2012/19/EU 

This  equipment should not be disposed as unsorted 

municipal waste. Contact a qualified recycler for 

disposal. 

 

 

 

 

 

 

 

 

 

 

 

LS-94 Connection Box for  

Public Lighting 

Installation Guide 

 

 

 

                    

 

 

 

 

 

 

LS-94   

 

5L2411 

 

 

 

 

 

Read this installation guide before installing the product 

 

 

 

 

 

 

83751 

/ EN1603

 

 

 

Technical Specification 

 

Safety and environmental conditions 

CE marking 

 

 

LV directive 2006/95/EC 

RoHS directive  2011/65/EU 

WEEE directive 2012/19/EU 

Standard

 

EN-IEC 61439-2:2011 

EN-IEC 60269-3:2013 

 

This product is designed to be safe under the following 

conditions: 

 

Specification 

Environmental conditions 

Operating temperature: 

Relative humidity: 

Protection degree: 

Installation class: 

Pollution degree: 

 

-5°C - +55°C 

5% - 85%, non condensing 

IP23 

1 (protective earth) 

Application conditions 

Umax: 

Frequency: 

Imax:    

Fuse: 

Strain relief: 

 

Maximum wire cross section 

and torque: 

 

 

 

Diameter ø  

Height  

 

230V (L-N) 

50Hz 

25A (mantle terminals) 

1x DII (E27), max 6A 

Yes, maximum 2 ground cables 

23mm and 2 light poles cords 

 

Terminal N, 1, 2, 3: 2x 10mm

2

, 2-

4Nm 

Terminal 4, 5: 2,5mm

, 1-2Nm 

Terminal 6, 7: 1,5mm

2

, spring 

94mm 

279,5mm 

Storage 

Temperature: 

Relative humidity: 

 

-20°C - +70°C 

5% - 85%, non condensing 

Approval 

 

Specification per type 

 

5L2411 

Fuse included 

No 

Phase selection 

Yes 

PE-N connection 

No 

Covered mantle 

terminals 

Yes 

Weight 

597gr 

Surge Protection 

Device (SPD) 

Citel MLPC1-230L-R* 

Protection level 10kA/10kV  

Spring terminal connection for max 1,5mm² 

*

 Please consult www.citel.fr for more information about the MLPC1- 230L-R

 

 

 

 

Please be aware, product liability, fulfilment to requirements and 

warranty are all expired when modifications on the product are made. 

 

ELEQ reserves the right to carry out modifications on its products, in 

order to improve them, without prior notice.  

Safety instruction 

All activities for installation, commissioning and maintenance of 

this connection box must be performed by qualified personnel 

that has the knowledge of applicable safety precautions. This 

guide assumes that the reader of this document has sufficient 

electro-technical knowledge to understand the content of this 

document. 

 

General 

The LS-94 is a connection box for public lighting and intended 

to  be used in lighting poles.  The connection box shall  be 

mounted in a weather protected and dry location. In the 

connection box the incoming (ground) cable can be connected. 

If desired, looped circuits wiring  to the next lighting pole is 

possible. The cable of the armature shall be connected on the 

outgoing terminals. 

 

Fuses protect the installation against overload  and short-

circuiting.  

 

Explanation of symbols 

 

This product is designed according to the 

EN-IEC 61439-2:2011  standards and meets the 

requirements of the Low Voltage Directive 2006/95/EC. 

 

 

Read the installation guide before mounting the 

product. Unprofessional work activities on electrical 

installations may result in a threat of danger to the life 

and health of human beings and livestock! 

 

 

RoHS Directive 2011/65/EU 

ELEQ states that it uses qualified components in its 

products only from manufacturers which meet the 

requirements of the European Directive for the 

"Restriction of use of certain Hazardous Substances 

 

 

WEEE Directive 2012/19/EU 

This  equipment should not be disposed as unsorted 

municipal waste. Contact a qualified recycler for 

disposal. 

 

 

 

 

 

 

 

 

 

 

 

LS-94 Connection Box for  

Public Lighting 

Installation Guide 

 

 

 

                    

 

 

 

 

 

 

LS-94   

 

5L2411 

 

 

 

 

 

Read this installation guide before installing the product 

 

 

 

 

 

 

83751 

/ EN1603

 

83751 / EN1603