C: Using the IEC61850 Protocol Ethernet Network Server
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
There are two overall parts to the implementation- the IEC 61850 Protocol Server and
GOOSE.
C.1.4.1: IEC 61850 Protocol Server
Following are features of EIG’s implementation of the IEC 61850 Protocol Server:
• The lower-level addressing uses PSEL=00000001, SSEL=0001, and TSEL=0001.
• At the server level, each implements a single Logical Device name formed by con-
catenating the IED name (chosen by the System Configurator) and "Meas" (ex,
"MyDeviceMeas").
• The Logical Nodes implemented within the Logical Device include the standard LLN0
and LPHD1 with optional standard logical nodes in the "M" class (ex, "MMXU") and
"T" class (ex, "TVTR"). Each Logical Node contains only standardized objects of
standardized types (Common Data Class, CDC). The device is based upon the first
edition of the IEC 61850 standards.
Examples of Logical Nodes within the Nexus® 1500+ family include eneMMTR1
(energy metering) and nsMMXU1 (normal speed Measurement Unit).
• The Nexus® 1500+ device will get its IED name from the first <IED> section in the
configuration file (.cid). This name will be used for accessing its access point (IP
address) and its single Logical Device named "Meas". The IED name can be com-
posed of any string of up to 32 (alphanumeric only) characters.
• The logical nodes implemented in the Nexus® 1500+ meter are listed below:
• The node LLN0 keeps common information for the entire logical device. In this
node Datasets and Reports can be defined, based on the limitations provided in
the ICD file: the Nexus® 1500+ meter supports up to 32 datasets with up to
256 attributes each, and up to 16 report control blocks. The report control
blocks and datasets must be configured in the CID file, although the options,
triggers and integrity period can be dynamically configured by IEC client. (The
Nexus® 1500+ meter does not support Journals.)
• The node LPHD1 defines physical parameters such as vendor, serial number,
device name plate and the software revision number.