Doc
#
E154713
11-3
11: Using the I/O Options
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
11.4: Pulse Output/RS485 Option Card (485P)
The Pulse Output/RS485 option card gives the meter 4 KYZ outputs that can be used
for counting operations, e.g., counting pulses from a gas or water meter to accumu-
late usage; and also gives the meter an RS485 Modbus communication port.
Pulse Output/RS485 Port Specifications
Dual RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard:
Type:
Two-wire, half duplex
Min. input impedance:
96 k
Ω
Max. output current:
±60 mA
Isolation between channels
AC 1500 V
Wh Pulse
4 KYZ output contacts:
Pulse width:
Programmable from 5 msec to
635
msec
Full scale frequency:
100 Hz
Form:
Selectable from Form A or Form C
Contact type:
Solid State - SPDT (NO - C - NC)
Relay type:
Solid state
Peak switching voltage:
DC ±350 V
Continuous load current:
120 mA
Peak load current:
350 mA for 10ms
On resistance, max.:
35
Ω
Leakage current:
1 µA@350 V