2: Meter Overview
2.7: Nexus® 1262/1272 Meter Logging Specifications
*Assumes logs store 4 scaled energy readings every 15 minutes.
**Number of events recorded (assumes 14 parameters monitored).
***Number of waveform records. Each record may be from 8 to 64 cycles in duration, depending upon
meter setup.
2.8: DNP3 Level 2
Nexus® 1262 and 1272 meters support DNP3 Level 2
DNP3 Level 2 Features
• Up to 104 measurements (64 Binary Inputs, 32 Binary Counters, 32 Analog Inputs)
can be mapped to DNP Static Points (over 3000) in the customizable DNP Point
Map.
• Up to 16 Relays and 8 Resets can be controlled through DNP Level 2.
• Report-by-Exception Processing (DNP Events) Deadbands can be set on a per-point
basis.
• Available Freeze commands are Freeze, Freeze/No-Ack, Freeze with Time, and
Freeze with Time/No-Ack.
• Freeze with Time commands enable the Nexus® meter to have internal time-driven
Frozen and Frozen Event data. When the meter receives the time and interval, the
data is created.
For complete details, download the appropriate DNP User Manual from our website at
www.electroind.com
.
Table 3:
Model
Historical
Log 1*
Historical
Log 2*
CBEMA/
ITIC**
Event
Log
**
Waveform
Log***
Flicker
Log**
Output
Log**
Input
Log
**
System
Events**
1272
555 Days
133 Days
512
1024
95
5120
256
1024
1024
1262
480 Days
133 Days
N/A
512
N/A
N/A
512
1024
1024