![Electro Industries/GaugeTech Nexus 1262 User Manual Download Page 178](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1262/nexus-1262_user-manual_2379732178.webp)
Doc# E151701 9-8
9: External I/O Modules
Electro
Industries/GaugeTech
™
Powered by Innovation™
9.5: Analog Transducer Signal Output Modules
9.5.1: Overview
The Analog Transducer Signal Output Modules (0±1 mA or (4–20) mA) are available
in either a 4- or 8-channel configuration. Maximum registers per request, read or
write, is 17 registers.
All outputs share a single common point. This is also an isolated connection (from
ground).
The Modbus Map for the Analog Output Module (and operating details) can be found in
the
Modbus Communicating I/O Modules
Manual.
Table 1:
Analog Transducer Signal Output Module Specifications
Model Numbers
1mAON4: 4-channel analog output 0±1 mA
1mAON8: 8-channel analog output 0±1 mA
20mAON4: 4-channel analog output (4-20) mA
20mAON8: 8-channel analog output (4-20) mA
Accuracy
0.1% of Full Scale
Scaling
Programmable
Communication
RS485, Modbus RTU
Programmable Baud Rates: 4800, 9600, 19200,
38400, 57600
Power Requirement
(12-20) V DC @ (50-200) mA
Operating Temperature
(-20 to +70)
o
C/(-4 to +158)
o
F
Maximum Load Impedance
0±1 mA: 10k Ohms; 4-20mA: 500 Ohms
Factory Settings
Modbus Address: 1mAON4: 128; 1mAON8: 128;
20mAON4: 132; 20mAON8: 132
Baud Rate: 57600
Transmit Delay Time: 0
Default Settings (Reset Button)
Modbus Address: 247
Baud Rate: 57600
Transmit Delay Time: 20 ms
Summary of Contents for Nexus 1262