Additional refrigerant charge
197
4
Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the
pressure for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it
indicates that there is moisture or leak source.
8. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ6.
35
Φ9.5
2
Formula
V=15g/m×(L-5)
V=30g/m×(L-5)
V: Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe
→ insulation (exc
ept joint
section) →
flare the pipe
→
piping layout and connection
→
vacuum drying
→ insulat
e the joint parts
9.1.2 Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
Temperature of gas pipe is very high (generally 50-100
℃
) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120
℃
According to the local law to choose insulation materials
The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Summary of Contents for DCI Light Commercial Series
Page 35: ...Service Space Indoor Units 35 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Page 41: ...Field Wiring Indoor Units 41 9 Field Wiring...
Page 44: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI KBD030 N11...
Page 46: ...Exploded View and Spare Part list 46 Indoor Units Exploded View of indoor unit ELSI KBD036 N11...
Page 48: ...Exploded View and Spare Part list 48 Indoor Units Exploded View of indoor unit ELSI KBD048 N11...
Page 59: ...Wiring Diagrams Indoor Units 59 4 Wiring Diagrams ELSI OCD012 N11 ELSI OCD018 N11...
Page 62: ...Wiring Diagrams 62 Indoor Units ELSI OCD048 N11 ELSI OCD060 N11...
Page 63: ...Static Pressure Indoor Units 63 5 Static Pressure ELSI OCD012 N11 OCD012...
Page 68: ...Static Pressure 68 Indoor Units ELSI OCD060 N11 OCD060 OCD060...
Page 73: ...Field Wiring Indoor Units 73 10 Field Wiring ELSI OCD012 N11 ELSI OCD018 N11...
Page 77: ...Exploded View and Spare Part list Indoor Units 77 Exploded View of indoor unit ELSI OCD018 N11...
Page 79: ...Exploded View and Spare Part list Indoor Units 79 Exploded View of indoor unit ELSI OCD024 N11...
Page 81: ...Exploded View and Spare Part list Indoor Units 81 Exploded View of indoor unit ELSI OCD030 N11...
Page 83: ...Exploded View and Spare Part list Indoor Units 83...
Page 85: ...Exploded View and Spare Part list Indoor Units 85 Exploded View of indoor unit ELSI OCD048 N11...
Page 87: ...Exploded View and Spare Part list Indoor Units 87 Exploded View of indoor unit ELSI OCD060 N11...
Page 92: ...Service Space 92 Indoor Units 3 Service Space...
Page 110: ...Dimensions 110 Indoor Units 2 Dimensions 270...
Page 111: ...Service Space Indoor Units 111 3 Service Space...
Page 116: ...Field Wiring 116 Indoor Units 10 Field Wiring ELSI KBD012 N11 ELSI KBD018 N11...
Page 126: ...Wiring Diagrams 142 Outdoor Units 4 Wiring Diagrams ELAU VLD012 H11...
Page 128: ...Wiring Diagrams 144 Outdoor Units ELAU VLD036 H13 ELAU VLD048 H13...
Page 129: ...Wiring Diagrams Outdoor Units 145 ELAU VLD060 H13...