Chapter 3 - Operation / Handling

3.1 General note

The guideline DIN EN 1717 will replace the DIN 1988-100. The „short-term connection“ of the heating system 
with mains water supply by a hose connection is then not longer state of the art. 

According to DIN EN 1717 chapter 5.3.2 : „All connections to the tap water installation are regarded as 
permanent connections“.

Therefore we recommend to install a safety armature with fluid class 4 when filling a heating system with 
CLARIMAX 1200 DM pH+ LED.

3.2 Comissioning

Starting with a new filter cartridge you always should displace air out of the water filter system and flush the 
filter system.

Please proceed as follows:

1.  Install filter cartridge in system, close system with filter-head and connect with hoses.
2.  Position filter system horizontally and let water run into connection „IN“. Rinse the filter with 10 liters water.
3.  Position the filter vertically and rinse with additional 10 liters of water.
4.  Dispose the rinsing water.

The filter-system is ready for operation after this procedure.

Repeat this process after any cartridge change.

3.3 Filling of heating systems

As soon as the system is ready for operation you can fill the heating system as usual. The filter treats the water 
in a single flow through principle. The inlet of CLARIMAX is to be connected to the mains tap water supply 
and the outlet of CLARIMAX with the heating system. Once the water has passed CLARIMAX it has the quality 
according to the guidelines. We recommend to install a system separator or a compact filling armature at the 
inlet of the CLARIMAX filter system.

3.4 In-line water correction

You even can treat existing heating water with the CLARIMAX filter system. Simply install CLARIMAX in a 
bypass and pump the heating water via CLARIMAX and back into the system, where the treated water will 
dillute the circulating system water. As a temporary limited but continuous process all the heating water will be 
corrected after a while. Please observe the maximum operation pressure and that the heating water should be 
in a quality of natural water without chemicals. The water must not contain strong oxidants. Particles should be 
removed by additional filtration at the inlet of CLARIMAX.

3.5 Capacity control

There is a conductivity meter installed in the filter head. This device controls the filter capacity and gives a 
signal, as soon as the cartridge is exhausted and needs to be replaced.

The end of capacity is indicated by an electrical conductivity of the treated water at a level of 90 - 100 µS/cm.

Page 8

www.elector-water-treatment.com

CLARIMAX 1200 DM pH+ LED – Water-filter-system for treatment of heating-system make-up water

Summary of Contents for Clarimax

Page 1: ...User Guide Water Filter System for Treatment of Heating System Make Up Water Water Treatment ...

Page 2: ...LARIMAX 1200 DM pH 5 2 Assembly Commissioning 2 1 System overview 6 2 2 Scope of delivery 7 2 3 Assembly of pressure container and container head 7 2 4 Assembly of inlet and outlet 7 3 Operation Handling 3 1 General note 8 3 2 Comissioning 8 3 3 Filling of heating systems 8 3 4 In line water correction 8 3 5 Capacity control 8 3 5 1 Integrated conductivity measurement 9 3 5 1 1 Battery and mains o...

Page 3: ...ar Anyone working with this device must read this manual completely and follow the instructions In addition to the operating instructions the locally applicable regulations for accident prevention and for safe and professional work must be considered The manufacturer of the water treatment systems recommends to run a written documentation at the side of use The user should record the date of filli...

Page 4: ...r system shall only be used by trained service technicians The manufacturer s specifications must be complied with for maintenance and or replacement of spare parts In case of unauthorized modifications at the device the CE declaration of the manufacturer expires The manufacturer takes no liability for damage caused by improper use Furthermore the warranty expires CLARIAMX must not be operated in ...

Page 5: ...IN EN 1717 at the inlet of CLARIMAX If the water pressure is higher than 6 9 bar a pressure limiter should be installed at the inlet of the water treatment system It is generally recommended to use a pressure limiter when filling heating systems At the water inlet of the filter head a DVGW model tested backflow preventer according to DIN EIN 13959 is factory installed The installation of all parts...

Page 6: ...r system 4 C to 50 C Ambient temperature for storage and transport dry new filter system 20 C to 50 C Nominal flow rate filter cartridge DM pH approx 300 l h at a pressure drop of 1 2 bar Weight dry wet 18 kg 24 kg Capacity 744 L at 500 µS cm conductivity of untreated tap water Dimensions Width Depth Height 288 255 550 mm Total system Operating position vertical Inlet connection G 3 4 Outlet conne...

Page 7: ...peration of this device Attention Please pay attention to the technical data and to the operation and security instructions prior assembly and comissioning After storage below 0 C Note Store only new dry cartridges below 0 C the product need to be stored at room temperature for at least 24 hours Chapter 2 Assembly Comissioning 4 5 Page 6 www elector water treatment com CLARIMAX 1200 DM pH LED Wate...

Page 8: ... head 3 counter clockwise lift it to the top to remove it from the housing Remove the red transport cap from the filter cartridge 2 and check the o ring seals for correct installation integrity and cleanliness Place cartridge 2 in pressure housing 1 Place both feet on the floor brackets 4 Place filter head 3 in position INSERT at pressure housing 1 Turn the filter head clockwise until it snaps bac...

Page 9: ...in a single flow through principle The inlet of CLARIMAX is to be connected to the mains tap water supply and the outlet of CLARIMAX with the heating system Once the water has passed CLARIMAX it has the quality according to the guidelines We recommend to install a system separator or a compact filling armature at the inlet of the CLARIMAX filter system 3 4 In line water correction You even can tre...

Page 10: ...n and charging of the battery pack 3 5 1 1 Battery and mains operation All functions are independently from the power supply The batteries are not charged in the state as delivered and therefore should be charged for at least 24 hours You can operate CLARIMAX either in mains supply mode with the power adapter or in battery mode A fully charged battery allows 48 hours operation You can find the con...

Page 11: ...hausted and that a replacement of the cartridge will soon be necessary The quality of the treated water is still within the range of VDI 2035 The third area is divided into 3 red LEDs All LEDs start flashing accompanied by an acoustic signal The yellow LEDs turn of The filter cartridge is exhausted and need to be replaced The quality of the water does not comply with VDI 2035 anymore 3 5 1 3 Stand...

Page 12: ...also confirmed acoustically The continuous measurement is only recommended in mains operation 3 5 1 6 Battery capacity The remaining battery capacity indicates the charge statues of the integrated rechargeable battery As the number of highlighted LEDS decreases the charge level decreases From green to red The 3 red LEDS always stay on and represent a critical state of charge The mains power adapte...

Page 13: ... can be disposed in accordance with local regulations 3 7 Warranty The CLARIMAX 1200 DM pH LED filter system is subject to the statutory warranty of 2 years A warranty claim can only be asserted if all instructions in this manual are followed and observed Damage caused by improper changes use or grossly negligent damage to the product are not covered by the warranty Malfunctions due to incorrect o...

Page 14: ...Page 13 www elector water treatment com CLARIMAX 1200 DM pH LED Water filter system for treatment of heating system make up water ...

Page 15: ...Page 14 www elector water treatment com CLARIMAX 1200 DM pH LED Water filter system for treatment of heating system make up water ...

Page 16: ...elector GmbH Düsseldorfer Straße 287 42327 Wuppertal Germany Phone 49 0 2058 1790863 Fax 49 0 2058 1790864 E Mail info elector gmbh de Internet www elector water treatment com Water Treatment ...

Reviews: