background image

© 

2013 eldoLED. All rights reserved. V2.4

More product documentation and eldoLED’s terms and conditions are available at www.eldoled.com.

Pay attention when connecting the LED groups:
• polarity reversal results in no light output and often damages the LEDs
• com and - of different groups damages the driver

 Wiring diagram POWERdrive 106/S                                                (PWR106S1) 

 

WARNING: Risk of electrical shock. May result in serious injury or death. Disconnect power before servicing or installing.

CAUTION: The device may only be connected and installed by a qualified electrician. All applicable regulations, legislation and build-
ing codes must be observed. Incorrect installation of the device can cause irreparable damage to the device and the connected LEDs.

120-277VAC

The driver accepts a universal mains voltage input of 120-277VAC, 
50/60Hz.

DALI

Use these connectors to connect the driver to a DALI network. Always 
combine a DA+ and DA- connector for either data input or data output. 

DMX in/LedSync out

Use these connectors when the driver is used in a DMX network. For 
DMX in, connect the network cable’s DMX+, DMX- and DMX shielding 
wire (the orange/white, orange and brown wire in a CAT5 cable) to the 
DMX in+, DMX in- and DMX in shield connector respectively. For 
LedSync out, connect the network cable’s DMX+, DMX- and DMX 
shielding wire to the LedSync out+, LedSync out- and LedSync shield 
connector respectively.

LED wire length

Maximum wire length from LED driver to LED engine at full load:

 

Ext in

You have the possibility to connect an external control device (0-10V 
control device, 10k

 potentiometer or show selection switch) to the 

driver’s Ext in+ and Ext in- connectors. Configure the driver for use 
with an external control device over the 3-button user interface.

LED groups

Indicates the location of the connectors for your LED groups. R(ed) 
represents channel 1, G(reen) represents channel 2, B(lue) repre-
sents channel 3 and W(hite) represents channel 4. The default group 
color allocation can be changed over the 3-button user interface. 

Output voltage vs output current for 4 outputs with symmetrical load

Vf

 typ

 is 57V, LED current ranges from 200mA - 1050mA

LEDcode/NTC

Use these connectors to connect a 47k

 NTC thermistor for closed 

loop LED engine temperature control.

AWG value

20

19

18

17

16

Distance  (m)

14

18

22

28

36

Distance (ft)

45.9

59

72.2

91.9

118.1

Please observe voltage drop over long wire lengths.

Longer wire lengths increase EMI susceptibility. 

0

1050

420

200

830

0

60V

30V

mA

Vf

 

 

4 LED groups,

4 control channels

LEDcode / NTC

+

-

+

-

+

-

DALI

{

N

L

VAC

120-277

{

DMX in shield

DMX in -

DMX in +

LedSync out shield

LedSync out -

LedSync out +

Ext in -

Ext in +

1

9 mm

0.35 inch

0.5-1.5 mm

2

AWG 20-16