background image

26

27

26

27

EN

EN

MANUAL ELDES ESIM264 V3.2

MANUAL ELDES ESIM264 V3.2

7. SYSTEM LANGUAGE

The system comes equipped with 2 languages for communication with the user by SMS text messages and a single language for EKB2 

keypad menu display. The default EKB2 menu language depends on ESIM264 firmware, which is based on the user’s location, while one of 

languages for communication by SMS text messages is always English.

List of currently available system languages (firmwares):

• Czech 

• English 

• Estonian 

• Finnish 

• French 

• Greek 

• Hungarian

• Icelandic 

• Italian 

• Latvian 

• Lithuanian 

• Norwegian

• Portuguese 

• Romanian

• Russian

• Slovak 

• Spanish 

• Swedish

To set a different SMS language, please refer to the following configuration methods.

Set SMS language

SMS

SMS text message content:

ll

Value:

 ll -

 SMS language, range - [CZ - Czech, EN - English, EE - Estonian, FI - Finnish, GR - 

Greek, HU - Hungarian, IC - Icelandic, IT - Italian, LV - Latvian, LT - Lithuanian, NO - Norwegian, 

PT - Portuguese, RO - Romanian, RU - Russian, SK - Slovak, SP - Spanish, SW - Swedish].

Example: 

SK

EKB2

Menu path:

OK 

 CONFIGURATION 

 OK 

 1470 

 OK 

 PRIMARY SETTINGS 

 OK 

 SMS LANGUAGE 

 OK 

 sms-lang 

 OK

Value: 

sms-lang 

– SMS language.

NOTE: 

  To obtain a firmware that features a different SMS and EKB2 menu language, please contact your local dealer. 

NOTE: 

  To change the language once the system has already been configured, you need to reset the device to the default configuration. For 

more details on how to do this, please refer to 

35.2. Restoring Default Parameters.

8. USER PHONE NUMBERS

The system supports up to 5 user phone numbers identified as User 1 through 5. When the phone number is set, the user will be able to 

arm/disarm the system by SMS text messages and free of charge phone calls (see 

12.1. Free of Charge Phone Call

 and 

12.2. SMS Text 

Message

) as well as to configure the system by SMS text messages. User phone numbers are also used to receive alarm phone calls and 

SMS text messages from the system (see

 17. ALARM INDICATIONS AND NOTIFICATIONS FOR USER)

By default, the system accepts incoming calls and SMS text messages from any phone number. Once a user phone number is listed, the 

system ignores any incoming calls and SMS text messages from a non-listed phone number as well as it rejects the SMS text messages 

containing wrong SMS password even from a listed user phone number (see 

8.1. System Control from any Phone Number

). To set User 

1 phone number is mandatory, while the other 4 are optional. The supported phone number format is the following: 

• 

International (w/o plus) – 

The phone numbers must be entered starting with an international country code in the following for-

mat: [international code][area code][local number], example for UK: 

4417091111111

.

Set user phone 

number

SMS

SMS text message content:

ssss_NRup:ttteeellnnuumm

Value: 

ssss

 – 4-digit SMS password; 

up

 – user phone number slot, range – [1... 5]; 

ttteeelln-

nuumm

 – up to 15 digits user phone number.

 

Example: 

1111_NR1:44170911XXXX1

EKB2

Menu path

:

OK 

 CONFIGURATION 

 OK 

 aaaa 

 OK 

 PRIMARY SETTINGS 

 OK 

 CALL/SMS SETTINGS 

 OK 

 USERS 

 OK 

 USER 1... 5 

 OK 

 PHONE NUMBER 

 OK 

 ttteeellnnuumm 

 OK 

Value:

 

aaaa

 – 4-digit administrator password; 

ttteeellnnuumm

 – up to 15 digits user phone 

number.

EKB3

Enter parameter 17, user phone number slot and phone number:

17 up ttteeellnnuumm  #

Value: 

up

 – user phone number slot, range – [01... 05]; 

ttteeellnnuumm

 – up to 15 digits user 

phone number.   

Example:

 170144170911XXXX1#

Config 

Tool

This operation may be carried out from the PC using the 

ELDES Configuration Tool

 software.

View user phone 

number

SMS

SMS text message content:

ssss_HELPNR

Value:

 

ssss 

– 4-digit SMS password.

Example: 

1111_HELPNR

EKB2

Menu path:

OK 

 CONFIGURATION 

 OK 

 aaaa 

 OK 

 PRIMARY SETTINGS 

 OK 

 CALL/SMS 

SETTINGS 

 OK 

 USERS 

 OK 

 USER 1... 5 

 OK 

 PHONE NUMBER   

 PHONE NUMBER

Value:

 

aaaa

 – 4-digit administrator password.

Config 

Tool

This operation may be carried out from the PC using the 

ELDES Configuration Tool 

software.

Delete user phone 

number

SMS

SMS text message content:

ssss_NRup:DEL

Value: 

ssss 

– 4-digit SMS password; 

up

 – user phone number slot, range – [2... 5].   

Example: 

1111_NR2:DEL

EKB2

Menu path:

OK 

 CONFIGURATION 

 OK 

 aaaa 

 OK 

 PRIMARY SETTINGS 

 OK 

 CALL/SMS 

SETTINGS 

 OK 

 USERS 

 OK 

 USER 2... 5 

 OK 

 PHONE NUMBER 

 OK 

 OK   

Value:

 

aaaa

 – 4-digit administrator password.

Config 

Tool

This operation may be carried out from the PC using the 

ELDES Configuration Tool

 software.

Summary of Contents for ESIM264

Page 1: ...ESIM264 GSM ALARM AND MANAGEMENT SYSTEM INSTALLATION MANUAL COMPLIES WITH EN 50131 1 GRADE 2 CLASS II REQUIREMENTS...

Page 2: ...off by disconnecting 2 pole switch off device of the mains power and disconnecting backup battery connector Fuse F1 type Slow Blown 3A Replacement fuses have to be exactly the same as indicated by th...

Page 3: ...UAB declares that this GSM alarm and management system ESIM264 is in compliance with the essential requirements and other relevant provisions of Directive 1999 5 EC Thedeclarationofconformitymaybecons...

Page 4: ...meter Configuration Main Settings Parameter Default Value Configurable by SMS EKB2 EKB3 Configuration Tool SMS and EKB2 Menu Language Depends on firmware version according to user s lo cation SMS Pass...

Page 5: ...re Exceeded Enabled System Shutdown Enabled Partitions Parameter Default Value Configurable by SMS EKB2 EKB3 Configuration Tool Partition 0 Name PART0 Partition 1 Name PART1 Keypad 1 4 Partition PART0...

Page 6: ...rted protocols Ademco Contact ID EGR100 Kronos Cortex SMS Dimensions 140x100x18mm 5 51x3 94x0 71in Operating temperature range 20 55 C 4 131 F Humidity 0 90 RH 0 40 C 0 90 RH 32 104 F non condensing 2...

Page 7: ...of an alarm the smoke detector could be reset by turning OFF and ON the PGM output C1 For more details please refer to 18 4 Turning PGM Outputs ON and OFF NOTE The system does NOT support 2 wire smoke...

Page 8: ...if EKB2 EKB3 keypad is used ATENTION The cable length for connection to 1 Wire interface can be up to 30m 98 43ft max 2 3 5 Temperature Sensor and iButton Key Reader Supported iButton key model Maxim...

Page 9: ...keypad please ensure that the set address of each keypad is different NOTE You may connect only 1 EKB2 EKB3 keypad or a mixed combination of EKB2 and EKB3 keypads The combination can consist of up to...

Page 10: ...e 0 50 mm2 0 02in2 1 thread unshielded cable of up to 100m 328 08ft length System Installation in ME1 Metal Cabinet 1 ME1 metal cabinet components Tamper switch to AC main power line to AC DC terminal...

Page 11: ...TION AND SIGNAL PENETRATION manual located at www eldes lt download 9 Power up the system 10 The system starts up in less than a minute Indicator STATUS should be flashing indicating successful micro...

Page 12: ...To navigate in the menu path touch keys to select the desired menu section and touch OK key to open the selected section To enter a required value use 0 9 keys and touch OK key for confirmation or can...

Page 13: ...server After the system configuration is complete use one of the following methods to end the configuration process Click Disconnect or Stop button and close ELDES Configuration Tool software The ses...

Page 14: ...from any phone number Once a user phone number is listed the system ignores any incoming calls and SMS text messages from a non listed phone number as well as it rejects the SMS text messages containi...

Page 15: ...S text message content ssss_STR OFF Value ssss 4 digit SMS password Example 1111_STR OFF EKB2 Menu path OK CONFIGURATION OK aaaa OK PRIMARY SETTINGS OK CALL SMS SETTINGS OK CTRL FROM ANY NUM OK DISABL...

Page 16: ...OK PASSWORD OK uuuu OK Value aaaa 4 digit administrator password uuuu 4 digit user code range 0000 9999 EKB3 Enter parameter 63 existing user code and new user code 63 vvvv uuuu Value vvvv 4 digit exi...

Page 17: ...Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software When adding of iButton keys is complete please disable Allow Adding New iButton Keys mode Disable...

Page 18: ...rresponding to the one that the user phone number is assigned to For more details on how to set user phone number partition please refer to 23 2 User Phone Number Partition CALL User ESIM264 30 12 2 S...

Page 19: ...gain during exit delay countdown To disarm the system by EKB3 keypad enter any out of 30 available 4 digit user codes using the number keys on the keypad When a valid user code is entered EKB3 keypad...

Page 20: ...key EWK1 EWK2 wireless keyfob or zone set up for Arm Disarm by Zone method user phone number that the system arming disarming by free of charge phone call was initiated from user phone number that th...

Page 21: ...pad and user code iButton key EWK1 EWK2 wireless keyfob Arm Disarm by Zone To arm the system without exit delay use one of the following system arming methods Free of charge phone call SMS text messag...

Page 22: ...physical zones intended for Panic button feature alarm activation upon pressing the button on EWK1 EWK2 wire less keyfob Virtual zones can be manually created using EL DESConfigurationToolsoftware 32...

Page 23: ...ple 280 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Set zone connection type for ATZ mode EKB2 Menu path OK CONFIGURATION OK aaaa OK ZONES OK...

Page 24: ...OK CONFIGURATION OK aaaa OK ZONES OK KEYPAD ZONES OK KEYPAD 1 4 ZONE OK STAY OK ENABLE OK EPGM1 zone OK CONFIGURATION OK aaaa OK ZONES OK EPGM1 ZONES OK EPGM1 ZONE 1 16 OK STAY OK ENABLE OK Value aaaa...

Page 25: ...d until the system is disarmed Once the system is disarmed the corresponding zone state will be indicated on the keypads see 31 1 1 EKB2 LCD Keypad and 31 1 2 EKB3 LED Keypad and Info SMS text message...

Page 26: ...GURATION OK aaaa OK ZONES OK EPGM1 ZONES EPGM1 ZONE 1 16 OK STATUS DISABLE OK Value aaaa 4 digit administrator password EKB3 Enter parameter 52 zone number and parameter status value 52 nn 1 Value nn...

Page 27: ...ed by one of the alarm messages in the home screen view ALARM FIRE ALARM 24H ALARM d During the tamper alarm EKB2 keypad will display TAMPER ALARM message in the home screen view e If one or more zone...

Page 28: ...istrator password EKB3 Enter parameter 30 and parameter status value 30 1 Example 301 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Enable call...

Page 29: ...Max number of PGM outputs per device Max number of PGM outputs in total On board PGM Outputs Built in wired PGM outputs of ESIM264 alarm system 4 4 EPGM8 PGM Outputs PGM outputs of EPGM8 hardwired PG...

Page 30: ...number and parameter status value 61 oo 1 Value oo PGM output number range 01 44 Example 61031 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Tur...

Page 31: ...when the PGM output action can begin End Time Determines the point in time when the PGM output action can complete On weekdays Determines days in week when the PGM output action is valid Additional Co...

Page 32: ...intend to manage the wireless devices by SMS text massage an 8 character wireless device ID code will be required in order to pair the device with the system or to remove it from the system The wirele...

Page 33: ...s 19 4 Disabling and Enabling Siren if Wireless Signal is Lost If a wireless device loses its wireless signal for 1 hour or longer the system will send notification by SMS text message to user phone n...

Page 34: ...ple 501 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Set EWF1 siren alarm duration Config Tool This operation may be carried out from the PC us...

Page 35: ...arming and disarming process After the system is successfully armed the siren bell will emit 2 short beeps and 1 long beep after the system is disarmed To enable disable the Bell Squawk feature please...

Page 36: ...quipped with a backup battery maintaining power supply of the system when the mains power supply is temporally lost The implemented feature allows the system to perform a self test on the backup batte...

Page 37: ...e mains power restore notification EKB2 Menu path OK CONFIGURATION OK aaaa OK SMS MESSAGES OK MAIN PWR REST EV OK DISABLE OK Value aaaa 4 digit administrator password EKB3 Enter parameter 25 notificat...

Page 38: ...partition determines which system partition s can be armed disarmed from a certain user phone number by dialing system s phone number Set user phone number partition EKB2 Menu path OK CONFIGURATION OK...

Page 39: ...2 Wireless Key fob Set EWK1 EWK2 partition Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software 24 TEMPERATURE SENSOR The system may be equipped with a...

Page 40: ...eter status value 25 14 1 Temperature fallen 25 15 1 Temperature exceeded Example 25151 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software 25 REMOTE...

Page 41: ...nfiguration methods Set periodic Info SMS frequency and time SMS SMS text message content ssss_INFO fff it Value ssss 4 digit SMS password fff frequency range 00 99 days it time range 01 23 Example 11...

Page 42: ...TION OK aaaa OK SMS MESSAGES OK ARMED EVENT OK DISABLE OK System disarmed OK CONFIGURATION OK aaaa OK SMS MESSAGES OK DISARMED EVENT OK DISABLE OK Mains power loss OK CONFIGURATION OK aaaa OK SMS MESS...

Page 43: ...system s SIM card The system will fail to reply if the credit balance is insufficient 28 EVENT LOG This feature allows to chronologically register up to 500 timestamped records regarding the following...

Page 44: ...olated high numbered zone or tamper number is 21 Zone LED section A flashing Zone LED section B steady ON Zone LED 1 1 Zone LED 7 12 Zone LED 2 2 Zone LED 8 18 Zone LED 3 3 Zone LED 9 24 Zone LED 4 4...

Page 45: ...ted 12 3146 Panic Silent zone restore Transmitted in case of zone of Panic Silent type is restored 13 1158 Temperature risen Transmitted in case of the temperature has increased above the MAX set valu...

Page 46: ...n 24 13 0 System shutdown Example 24080 Config Tool This operation may be carried out from the PC using the ELDES Configuration Tool software Enable data message EKB2 Menu path General alarm restore O...

Page 47: ...tem has not received the ACK data message from the monitoring station within 35 seconds SMS The system has not received the SMS delivery report from the SMSC Short Message Service Center within 45 sec...

Page 48: ...nge 0 65535 seconds EKB3 Enter parameter 69 and duration of delay after last attempt 69 aaapp Value aaapp duration of delay after last attempt range 0 65535 seconds Example 69200 Config Tool This oper...

Page 49: ...t administrator password EKB3 Enter parameter 43 and protocol number 43 0 TCP 43 1 UDP Example 431 NOTE KronosNET KronosLTsoftwarecommunicatesviaTCPprotocol whileEGR100middle warev1 2andupsupportsboth...

Page 50: ...ntify the alarm system unit by ESR100 digital receiver or EGR100 middle ware It is MANDATORY to change the default Unit ID before using ESR100 or EGR100 Set unit ID EKB2 Menu path OK CONFIGURATION OK...

Page 51: ...phone numbers for communication with the alarm system by CSD communication method Tel Number 1 is mandatory the other four can be used as backup phone numbers and are not necessary The supported phon...

Page 52: ...see 23 3 Keypad Partition and Keypad Partition Switch Audio indication by built in buzzer Wireless device information display see 19 2 Wireless Device Information Temperature display see 31 1 1 1 Ico...

Page 53: ...999 ENGLISH second lang 0 23 1 65535 1 65535 1 65535 1 65535 seconds 1 10 0 65535 0 65535 seconds seconds seconds seconds seconds seconds minutes 0 99 yyyy mm dd hr mn INTERIORFOLLOWER INSTANT 24 HOUR...

Page 54: ...lnnuumm ttteeellnnuumm 15 digits 15 digits 15 digits DISABLE ENABLE DISABLE ENABLE DISABLE ENABLE DISABLE ENABLE DISABLE ENABLE DISABLE ENABLE Continued in next page DISABLE ENABLE Continued from prev...

Page 55: ...T N A 31 2 1 Wire Interface 1 Wire interface is used for the system to communicate with an iButton key reader and a temperature sensor 1 Wire interface COM and DATA terminals are ground and data respe...

Page 56: ...0 47in 31 3 2 2 Installation 1 Disconnect ESIM264 alarm system mains power and backup battery 2 Insert EA2 pins into appropriate ESIM264 alarm system slots ESIM264 EA2 47 3 Connect a speaker to EA2 Sp...

Page 57: ...cified FTP server address where the firmware file is hosted and begins downloading and re flashing the firmware The firmware file must be located in a folder titled Firmware In order to initiate the u...

Page 58: ...messageissenttotheuser thesystemmust know that the message was successfully delivered The only way to partly disable the SMS delivery report for alarm notifications only is to enable alarm SMS notific...

Page 59: ...D1T plastic enclosure with iButton key reader and temperature sensor EWS2 wireless external siren EWF1 wireless smoke detector EWK1 wireless keyfob EW2 wireless zone and PGM output expansion module EW...

Page 60: ...MadeintheEuropeanUnion www eldes lt...

Reviews: