Model
WSD01-04A01
Technical data
Supply voltage:
max. 11.5 - 20.5 V DC
via DALI-Bus
Connection:
Spring terminal
Line 0.2 - 0.75 mm²
rigid or flexible
Current consumption:
17 mA
Operating temperature:
-20 °C to +60 °C
Dimensions:
Key: 55x55x9 mm
or
Keys: 27x55x9 mm
Mounting plate:
71x71x1.5 mm
Weight:
30.0 g
System requirements:
Windows Vista, 7, 8, 10
USB 1.1 or higher
10 MB free hard drive space
Scope of delivery
DALI module, mounting plate, 1x single-button unit, 2x
serial button unit, attachment set, operating instructions
Intended use
The device must only be used as a wall-mounted button unit
for controlling DALI end devices.
The manufacturer is not liable for any damage caused by
improper or unintended use!
Safety information
Before connecting this device, please read these
instructions carefully!
Observe any applicable laws, standards and regulations
as well as manufacturer instructions pertaining to the de-
vices being connected!
Have any malfunctioning devices inspected by the manu-
facturer!
Do not perform unauthorised modifications to the device!
Function
The DALI wall-mounted button unit enables up to four DALI
functions to be triggered via the DALI bus. (DALI: Digital Ad-
dressable Lighting Interface).
When using one-button operating modes, a maximum of four
DALI devices or four DALI groups can be addressed.
When using two-button operating modes, the number of ad-
dressable devices or groups is reduced to two.
It is also possible to simultaneously control all devices on the
DALI bus (broadcast) in any mode.
WSD01 Wall-mounted button unit DALI
D
The WSD01 DALI wall-mounted button unit can be used as a
single-button controller or as a serial button controller.
The "WSD01 Configurator" software is used to allocate indi-
vidual functions to the individual buttons.
Each individual button can have a function allocated to it:
-
DIM two-button operation,
-
ON/OFF two-button operation,
-
DIM one-button operation,
-
ON/OFF one-button operation,
-
Open SCENE,
-
SKIP through scenes,
-
DEAD MAN'S SWITCH one-button operation,
-
Fixed dimmer setting.
The function “DIM two-button operation” is configured as a
factory preset for broadcasting to all DALI devices on the
bus.
This enables the wall-mounted button unit to be used on the
DALI bus without any prior programming using the “WSD01
Configurator”.
The RGD-ACC-01 set-up cable (including “WSD01 Configu-
rator”) is required to modify function and address allocations.
This is not included with the product and must be ordered
separately.
Connecting the wall-mounted button unit with
the PC
To enable the DALI wall-mounted button unit to be config-
ured using the PC, the RGD-ACC-01 set-up cable is re-
quired (see Figure 1).
1. Remove the cover panel and the WSD01 from the
mounting plate if necessary.
2. Insert the enclosed programming adapter into the DALI
end of the set-up cable.
3. Connect the 4-pin programming adapter to the rear of
the WSD01. The connectors are protected from being
inserted the wrong way around.
4. Insert the USB plug of the set-up cable into a free USB
port on the PC.
5. Install and launch the "WSD01 Configurator" configu-
ration software.
Single-button
controller
Serial button
controller
E
F
A
B1
D
B2
I
(siehe Abb. 1)
A
Button(s)
B1 DALI module, front
B2 DALI module, rear
D
Cover frame,
cut-out dimensions 55x55 mm
(not included in scope of delivery
)
E
Mounting plate
F Clip
G
Programming adapter
H
Programming cable RGD-ACC-01
I
Connection terminal (DALI terminals)
(recommended removal tool: SMDflat WKZ)
PC
Fig. 1
Power supply DALI bus
G
H
Disposal
Waste electronic equipment must not be disposed of
with household waste!
Dispose of the waste equipment via collection
facilities for electronic scrap or via your special-
ist dealer.
Dispose of packaging material in the recycling
bins for cardboard, paper and plastic.
Warranty
Within the statutory warranty period, we undertake to rectify
free of charge by way of repair or replacement any product
defects arising from material or production faults.
Any unauthorised tampering or modifications will render this
warranty null and void.
Conformity
Hereby, ELDAT GmbH declares that the radio equipment
type WSD01 is in compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available
at the following internet address: www.eldat.de
Customer service
If, despite proper handling, the device does not work prop-
erly or if the device has been damaged, please contact the
manufacturer or your retailer.
ELDAT GmbH
Im Gewerbepark 14
15711 Königs Wusterhausen / Germany
Phone:
+ 49 (0) 33 75 / 90 37-310
Fax:
+ 49 (0) 33 75 / 90 37-90
Internet: www.eldat.de
Email:
Preparing the wall-mounted button unit for operation
General information
1. Attach the mounting plate to the installation location
using the enclosed screws & wall plugs or the adhesive
pads.
2. Connect the WSD01 to the DALI bus via the DALI termi-
nals on the rear. The direction is interchangeable.
3. Place the cover frame on the mounting plate and lock
the DALI module into place at the top and bottom onto
the clips. The arrow on the module must be pointing
upwards.
4. Plug your chosen button unit (single-button or serial
button controller) onto the transmitter module.
5. (optional) Program the functions and addressing of
the WSD01 using the RGD-ACC-01 set-up cable and
"WSD01 Configurator".