Trinox Floor Standing Shell and Tube Boiler
8 L344
©
Elco UK 04/07/2012
IDENTIFICATION ELEMENT
The appliance can be identified through the DATA PLATE this contains the operating values and
identification data. The plate is applied in the front upper part, on the right.
For any servicing and spare parts the correct identification of the boiler model will facilitate
ordering of the correct parts
IMPORTANT: ensure that the boiler is provided with a data plate. If not, please request a data
plate from the suppliers.
LIST OF SPARE PART
The spare parts recommended for two years of operation are the following
n.1 working thermostat
n.1 safety thermostat
n.3 inspection doors gasket kit
n.3 hand hole gasket
n.3 manhole gasket (only models from 5000 to 9000)
n.1 flame sight glass
n.1 flame sight glass gasket
INSTALLATION
The boiler must be installed in a room that complies with the provisions and minimum distances
established by the current regulations and is provided with suitably sized air vents.
The boiler must be positioned on a flat surface capable of uniformly supporting
the base structure section bars.
The surface should be raised from the floor.
CAUTION: if the burner is powered with combustible gas with specific gravity higher than the
specific gravity of air, the electrical parts must be positioned above 0.5 metres from ground level.
The boiler must not be installed outside as it has not been desi gned for outdoor installation and is
not provided with automatic anti-freeze systems
DISCHARGE OF COMBUSTION PRODUCT
The use of the correct burner/boiler/flue drastically reduces consumption, optimises combustion
with low emission of contaminants and provides effective protection against condensation.
The FLUE must be resistant to heat and condensation, thermally insulated, hermetically sealed,
without bottlenecks or obstructions, as vertical as possible and sized according to current
regulations.