Trinox Floor Standing Shell and Tube Boiler
19 L344
©
Elco UK 04/07/2012
Check the efficiency of safety and control instruments.
Never leave highly inflammable substance containers in the premises where the boiler has been
installed.
TROUBLESHOOTING
Below is the description of the most common faults and their remedy:
FAULT: the burner does not turn on.
REMEDY:
-
check electric connections;
-
check the regular fuel supply
-
check the integrity and the cleanness of the fuel supply system and that no air is present;
-
check that ignition sparks form regularly and the burner appliance works correctly;
-
check the boiler safety thermostat intervention with manual reset;
-
check the calibration of the environment thermostat.
FAULT: the burner turns on well but turns o ff immediately after.
REMEDY:
check the pilot flame, the air calibration and that the burner appliance works correctly.
FAULT: the burner is difficult to be adjusted and/or no output.
REMEDY:
-
check for the cleanness of burner, boiler, boiler/flue pipes and flue;
-
check the hermetic seal of the smoke circuit (door, burner plate, smoke box, boiler/flue
connection);
-
check that the fuel supply is flowing regularly and verify the effective power of the burner;
-
check for the presence of scale and carry out a ch emical washing.
FAULT: the boiler gets easily covered with so ot.
REMEDY:
-
check the burner regulation (smoke analysis);
-
check the fuel quality;
-
check the flue for clogging and the cleanness of the burner air intake (dust).
FAULT: smell of gas and/or unburnt products.
REMEDY:
-
check the seal of the fuel supply system (if gas fuel);