6.4 PROFIBUS-DP Slave
Ko
rr
ek
tu
ra
us
dr
uc
k
6.4.2
Parametrization
Table 6-10: Parameters of the PROFIBUS-DP slave
Baudrate
Functional starting parameter; the baud rate is determined
automatically. If this is not possible, the system shows 0.
Possible values in kBaud: 12000(12 MBaud), 6000(6 MBaud),
3000(3 MBaud), 1500(1.5 MBaud), 500(500 kBaud), 187(187.5
kBaud), 93(93.75 kBaud), 9(9600 Baud), 0(automatic termination
not possible).
State
State of the Profibus module. The firmware-internal error codes of
the Profibus object are shown.
No
Designation
Unit
Data
type
E/A
Default
1
Baudrate
kBaud
DINT
AF
2
State
DINT
AD
3
Version
String(33)
AF
4
IOAddress
DINT
AK
16#D8000
5
ErrorCode
USINT
AD
6
ErrorCount
UINT
AD
7
ModState
USINT
AD
8
DataExMode
DINT
ERC
2
9
IOTrigger
DINT
ERC
3
10
CycleLoad
ns
DINT
AD
11
IRQ
DINT
ERC
7
12
Format
DINT
EDC
INTEL
13
IOReset
DINT
EDC
2
Error
code
Meaning
-900
When accessing the dpm range of the Profibus, the admissible
range was exceeded. It was attempted to send or receive a byte with
a number greater than 511.
-901
No Profibus recognized (CIF not found). Either no module is
plugged, or a wrong address was set.
-902
A timeout occurred when waiting for the ready bit of the module after
initializing the Profibus hardware.