6.5.3.5
Scenes function
This folder is enabled if
Channel X
Main parameters
Scenes function =
enabled
.
Parameter name
Conditions
Settings
Download overwrites
learned behavior
Scenes function = enabled
no
/
yes
Defines whether the download of a program on the device should erase and overwrite the stored scene
output values previously learned and stored in the device.
When the device is put into operation for the first time, this parameter should be set to "yes" (default
value) so that the output is initialized with valid scene values. Otherwise, the values are set to “0” (off)
for all scenes.
Scene
n
Scenes function = enabled
enabled /
disabled
Enables or disables a new scene code to be assigned to the output.
Scene
n
–
Scene number
Scenes function = enabled
Scene n = enabled
1…64
(
1
)
Scene number to be assigned to the output. The output will respond to scene commands that match
the specified number.
Scene
n
–
Output behavior
Scenes function = enabled
Scene n = enabled
off /
on
(Initial) output value for the selected scene. This value will be possibly overwritten by a scene “store”
command i
f the “Learning mode” option is enabled.
Scene
n
–
Light intensity %
Scenes function = enabled
Scene n = enabled
1..100% slider
(
50%
)
Specifies the dimming value for the selected scene.
Scene
n
–
Activation delay
Scenes function = enabled
Scene n = enabled
hh:mm:ss.ff
(
00:00:00.00
)
Delay between a scene
“recall” command and the actual output switching.
The maximum value is 01:49:13.50.
Scene
n
–
Learning mode
Scenes function = enabled
Scene n = enabled
disabled
/ enabled
When
disabled, the scene “store” commands are ignored and only the output values set in the
configuration are used.
Each scene recall telegram restarts the activation delay.
If a new scene recall telegram is received while a delay is active (scene recall not yet
executed), the old - and not yet recalled - scene will be rejected and the newest scene value
will be in effect.
The scene recall delay has no influence on the saving of scene values when the learning
mode is active.
If the same scene number is set for several scene entries, only the scene with the lowest
entry number (1...8) will be considered. The other internal scenes will be ignored in this case.
The scene recall can be overridden by a
forced control
or a
lock
function.