Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 29
6.5.3
Channel x configuration
6.5.3.1
Main parameters
Parameter name
Conditions
Settings
Load type
-
incandescent lamp (R)
with electronic transformer (RC)
with magnetic transformer (RL)
Specifies the type of electrical load that the dimmer is expected to drive.
Please make sure to specify the correct value in order to prevent malfunctions of the device.
Full range
dimming time
-
hh:mm:ss.fff
(
00:00:04.000
)
The time it takes the dimmer to bring the output value from 0% to 100%; in other words, the speed of
the brightness variation when the setpoint is changed
through an “up/down” type command.
Changing the absolute setpoint has immediate effect on the output value.
Minimum dimming value
%
-
1..100% slider
(
50%
)
Allows to ensure that, in the “ON” state, the output guarantees a minimum brightness level.
Intensity when switch on
-
last value
new value
Specifies the output value when the output is switched on through a bus command.
Intensity when switch on
–
Light intensity %
Intensity when switch on = new value
1..100% slider
(
50%
)
Specifies the new value for switch-on.
Switch on type
-
instant on
soft
Specifies whether the device should reach the setpoint gradually when the output is switched on.
Ramp time for on
Switch-on type = soft
hh:mm:ss.fff
(
00:00:02.000
)
Specifies the transition time at switch-on.
The specified time refers to the time required to complete an excursion from 0% to 100%. For example,
if you set the value 00: 01: 00: 000, to bring to 50% the corresponding output it takes 30 s.
Switch off type
-
instant off
soft
Specifies whether the device should reach the zero brightness state gradually when the output is
switched off.
Ramp time for off
Switch-off type = soft
hh:mm:ss.fff
(
00:00:02.000
)
Specifies the transition time at switch-off.
The specified time refers to the time required to complete an excursion from 100% to 0%. For example,
if you set the value 00: 01: 00: 000, to bring to 0% the corresponding output, starting from 50%, it takes
30 s.
Behavior at
power on
-
off
on
no change
previous value
Allows to determine the value of the output to be set when the power is first applied or returns after a
power fail.