Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 27
6.5 Device settings
This section lists all configurable parameters and describes related communication objects.
Every channel offers the same set of communication objects and parameters, but they may all be
independently configured. Hereafter, a generic channe
l number is referenced as “x” (where x = 1…2).
The parameter values highlighted in bold represent the default value.
The device settings are divided in three main groups: the general device settings, the general channel
configuration settings and the channel-specific settings.
6.5.1
General device configuration
Parameter name
Conditions
Settings
Manual operation
-
enabled
disabled
Enables the front panel pushbutton that activates manual mode.
Disable from bus
Manual operation = enabled
yes
no
Allows to disable manual mode through a bus command
Restore auto mode time
Manual operation = enabled
Disable from bus = yes
hh:mm:ss
(
00:15:00
)
Sets the time after which the manual operation mode is reverted to automatic.
A zero time duration (00:00:00) means that the device may remain in manual mode indefinitely.
Power off alarm
-
enabled
disabled
Makes an alarm communication objects available which signals when the bus power supply fails.
Object name
Conditions
Size
Flags
DPT
CO number(s)
Disable front pushbuttons
Manual operation = enabled
Disable from bus = yes
1 bit
C-W--
[1.002] boolean
0
Power off alarm
Device power off alarm =
enabled
1 bit
CR-T-
[1.005] alarm
1