7.12.2
Presence sensors
The
Presence sensors
folder includes the following parameters:
Presence sensors function
Presence sensors use
Thermostat modes
Absence time to switch HVAC mode
For this function external sensors (from bus) can be used, such as the ekinex EK-SM2-TP movement sensor
or the ekinex EK-DX2-TP (X = B, C, D, E) presence sensor. The following condition has to be true:
o
External sensors (from bus)
Presence sensor 1 and/or Presence sensor 2 = enabled
7.12.2.1
Parameter and communication object tables
Parameter name
Conditions
Values
Presence sensors function
disabled
/ enabled
Parameter that enables the presence sensor function.
Presence sensors use
Presence sensor function = enabled
comfort extension
comfort limitation
comfort extension and comfort
limitation
Thermostat modes
Presence sensor function = enabled,
Presence sensors use = comfort
extension and comfort limitation, or
comfort limitation
comfort-standby
comfort-economy
Absence time to switch HVAC mode
Presence sensor function = enabled
00:01:00 hh:mm:ss
[range 00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode set in the
Thermostat modes parameter
.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Presence sensor 1 (from bus)
Presence sensor function=
enabled
1 bit
C-WTU
[1.018]
occupancy
30
Presence sensor 2 (from bus)
Presence sensor function =
enabled
1 bit
C-WTU
[1.018]
occupancy
31