Application manual
KNX room temperature controller EK-EQ2-TP
Release 3.00 - Updating: 27/06/2017
Application Manual
© SBS S.p.A. - All rights reserved
Page 72
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Windows contact sensor 2
(from bus)
Window contacts function =
enabled,
Window contact 2 = enabled
1 Bit
C-W--
[1.019]
window/door
44
7.11.2
Presence sensors
The
Presence sensors
folder includes the following parameters:
Presence sensor function
Presence sensors use
Thermostat modes
Absence time to switch HVAC mode
For this function only use external sensors (from bus) can be used, such as the ekinex EK-SM2-TP
movement sensor or the ekinex EK-DX2-TP (X = B, C, D, E) presence sensor. The following condition has to
be true:
External sensors (from bus)
Presence sensor 1 (from bus) or Presence sensor 2 (from bus) = enabled
7.11.2.1
Parameters and communication objects
Parameter name
Conditions
Values
Presence sensor function
disabled
/ enabled
Parameter that enables the presence sensor function.
Presence sensors use
Presence sensor function = enabled
comfort extension
comfort limitation
comfort extension and comfort
limitation
Thermostat modes
Presence sensor function = enabled,
Presence sensors use = comfort
extension and comfort limitation or =
comfort limitation
comfort-standby
comfort-economy
Absence time to switch HVAC mode
Presence sensor function = enabled
00:01:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode set in the
Thermostat modes parameter.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Presence sensor 1 (from bus)
Presence sensor function=
enabled
1 Bit
C-W---
[1.018]
occupancy
32
Presence sensor 2 (from bus)
Presence sensor function =
enabled
1 Bit
C-W---
[1.018]
occupancy
33