CD30 / CD30E 

INDUSTRIAL DEHUMIDIFIER 

OWNER’S MANUAL 

 
 

 

 
 
 
 
 
 
 
 
 
 

www.eipl.co.uk  

Product Support Questions: Contact Ebac USA at (757) 873 6800

Sales Inquiries: Contact Sylvane at (800) 934-9194 or visit sylvane.com

Summary of Contents for CD30

Page 1: ...TPC226 Issue 5 Date 05 01 12 CD30 CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk Product Support Questions Contact Ebac USA at 757 873 6800 Sales Inquiries Contact Sylvane at 800 934 9194 or visit sylvane com ...

Page 2: ... point Moisture forms on the evaporator coil and is collected in the condensate tray which is equipped with a permanent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature ...

Page 3: ...Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CD30 CD30E HEIGHT 12 WIDTH 12 DEPTH 22 WEIGHT CD30 50 lbs CD30E 55 lbs AIRFLOW 170 CFM MAX OPERATING TEMP 95ºF POWER SUPPLY 110V 60Hz CURRENT CD30 4 A CD30E 5 A REFRIGER...

Page 4: ...unning d Leave the machine running for 15 minutes e Observe the evaporator coils to confirm frost formation i If the air temperature is below 70ºF an even coating of frost should cover the entire evaporator coils except for the last one or two coils ii If the temperature is above 70ºF frost and or droplets of condensed water should cover the entire evaporator coil If after carrying out all the abo...

Page 5: ...across its surface At temperatures above 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 To check the operation of the defrost system switch the machine on and leave it running for approximately 45 minutes The machine will then ...

Page 6: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Page 7: ...Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center 4 Contact the Factory Service Center Little or no defrost when required 1 Faulty Timer 2 Faulty bypass timer 1 Contact the Factory Service Center 2 Contact the Factory Service Center Unit vibrates excessively 1 ...

Page 8: ... Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Tel 44 0 1388 664400 Fax 44 0 1388 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Produ...