Appendix 1 Specifications
Model
Capacity
100kVA
90kW
120kVA
108kW
160kVA
144kW
200kVA
180kW
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
208~478Vac
Frequency Range
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage:220V:+25%( op10%,+15%,+20%);
230V:+20%( op10%,+15%);
240V:+15%( op10%);
Min. voltage:-45%(optional -20%,-30%)
Frequency protection range: ±10%
Output
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
0.9
Voltage Regulation
±1%
Frequency
Utility
Mode