Parameterisation
MSM-USM2G-BA-UK-001
Page 41 of 46
5.3 Main menu Configuration
This menu contains buttons with the following functionalities:
Accept configuration
Storage and activation of the changed parameters in the fault annunciators.
After finishing
the parameterisation, the new parameters have to be accepted and thus stored into the
device.
Accept all 4 configurations
With this button the parameters of all devices (base device and optionally defined slave
dev
ices (annunciator 1 …3)) will be accepted and stored.
Dismiss configuration
Dismissal of all changes done in the session (since last “accept configuration”).
EES factory defaults
Restoring of the default values for all parameters. (Note: also the IP-address of the
annunciator will be set to the default value!)
5.4 Parameterisation by push buttons
The annunciators of the series USM can temporarily be reset to the default settings by means of the
push buttons on the device front. This allows to reset all parameters of the device, e.g. to enable
communication to the annunciator for maintenance access.
The default parameters can be restored as follows:
1.
Press button 1 and 4 (the topmost button (=1) and the lowermost button (=4)) at the same
time for approx. 2 seconds.
2.
The top-left LED shows orange light, the LED underneath it shows red light, the horn sounds
for a moment and the OK-LED starts flashing in red and green. This indicates that the
annunciator now is in parameterization mode.
3.
Now press button 3 (3
rd
button from the top) one or two times (dpeneding on the currently
activated parameter set: press once if parameters deviate from the default parameters, press
twice if the default parameters are active) until the second LED in the left column of LEDs
shows green light. This indicates that all parameters of the annunciator will now be set to
default.
4.
In the next step please confirm this by pressing the lowermost button (button 4).
5.
Now the indication of the annunciator goes back to the normal operation state (you have left
the parameterization mode) and you can log on to the web-server under the default IP
address (192.168.1.99).
For devices with integrated IT security functionalities (options
“S“ and “P“), also the
security relevant settings (port settings, passwords) will be reset to the default values.